Section 6 • Troubleshooting

Section 6 • Troubleshooting

Table 6-1. Slide Valve Actuator Troubleshooting Guide (1 of 2)

Problem

Reason

Solution

 

Dirt or debris is blocking one or both

Clean the optocoupler slots with a

 

optocoupler slots

Q-Tip and rubbing alcohol.

 

 

Adjust the photochopper so that

 

 

the fence extends further into the

 

The photochopper fence extends

optocoupler slots. Make sure the

 

motor brake operates freely and

 

less than about half way into the

 

the photochopper will not contact

 

optocoupler slots

 

the optocouplers when the shaft is

 

 

 

 

pressed down.

 

 

 

The actuator cannot be calibrated or

The white calibrate wire in the grey

Tape the end of the white wire in the

panel and make sure that it cannot

exit calibration mode

Turck cable is grounded

 

touch metal

 

 

 

Dirt and/or condensation on the

Clean the boards with an electronics

 

position sensor boards are causing it

 

cleaner or compressed air.

 

to malfunction

 

 

 

The calibrate button is stuck down

Try to free the stuck button.

 

The position sensor has failed

Replace the actuator.

 

 

 

 

 

 

Push button is being held down for

Depress the button quickly and then

 

more that ¾ second when going

 

let go. Each ¾ second the button is

 

through the calibration proce-

 

held down counts as another press.

 

dure

 

 

 

The white calibrate wire in the

Tape the end of the white wire in the

 

grey Turck cable is grounding

panel and make sure that it cannot

 

intermittently

touch metal.

 

 

Tape the end of the white wire in the

The actuator goes into calibration

A very strong source of electromag-

panel and make sure that it cannot

netic interference (EMI), such as a

touch metal.

mode spontaneously

contactor, is in the vicinity of the ac-

Install additional metal shielding ma-

 

 

tuator or grey cable

terial between the EMI source and

 

 

the actuator or cable.

 

There is an intermittent failure of the

 

 

position sensor

Replace the actuator.

The actuator goes into calibration

The motor brake is not working prop-

Get the motor brake to where it

mode every time power is restored

erly (see theory section above.)

operates freely and recalibrate.

after a power loss

 

 

 

 

The motor was manually moved

 

 

while the position sensor was not

Recalibrate.

The actuator does not transmit the

powered.

 

 

 

The motor brake is not working

Get the motor brake to where it op-

correct position after a power loss

properly

erates freely and then recalibrate.

 

 

 

 

 

The position sensor’s EEPROM

Replace the actuator.

 

memory has failed

 

 

 

 

 

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG