Oil System Components

Section 5 • Maintenance/Service

Oil System Components

Oil Sampling

WARNING

When working with LFG, NG or other dangerous or flammable gases, ensure there are adequate ventilation and vapor detectors. Refer to national fire and building codes. Failure to comply may result in serious injury or death.

NOTE

A copy of the oil analysis report is also sent to Vilter. See Appendices for a sample of the oil analysis report.

An oil analysis report will show the physical properties of the oil, such as:

Water content

Viscosity

Acid number

Particle count

WARNING

Antioxidant level

 

Avoid skin contact with any condensate or oil. Wear

Wear metals

 

 

rubber gloves and a face shield when working with

Contaminate/additive metals

condensate or oil. Failure to comply may result in

 

 

serious injury or death.

 

 

Use Vilter Oil Analysis Kit (VPN 3097A) to collect an oil

 

 

sample for analysis. For an example, see Figure 5-2. Fill

 

 

out label for bottle. Place in mailing tube and seal with

 

 

the preaddressed mailing label. Below are a few points

 

 

to remember when taking a sample:

 

 

• Sample running compressor units, not cold units.

 

 

• Sample upstream of the oil filter.

 

 

• Create specific written procedures for sampling.

 

 

• Ensure sampling valves and devices are thoroughly

 

 

flushed prior to taking a sample.

 

 

• Ensure samples are taken as scheduled in the

 

 

Maintenance and Service Schedule.

 

 

• Send samples immediately to the oil analysis lab after

 

 

sampling, do not wait 24 hours.

 

 

Figure 5-2. Oil Analysis Kit

5 – 4

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Page 62
Image 62
Emerson VSSG Oil System Components Oil Sampling, Maintenance/Service, sample for analysis. For an example, see -2. Fill