Table 6-1. Slide Valve Actuator Troubleshooting Guide (2 of 2)

Section 6 • Troubleshooting

Table 6-1. Slide Valve Actuator Troubleshooting Guide (2 of 2)

Problem

Reason

Solution

 

The motor was manually moved

 

 

while the position sensor was not

Recalibrate.

 

powered.

 

The actuator does not transmit the

The motor brake is not working

Get the motor brake to where it op-

correct position after a power loss

properly

erates freely and then recalibrate.

 

 

 

 

 

The position sensor’s EEPROM

Replace the actuator.

 

memory has failed

 

 

 

 

 

 

The photochopper is misaligned

Try to realign or replace the actuator.

 

with the slotted optocouplers

 

 

 

 

 

There is a rapid clicking noise when

The photochopper is positioned too

Adjust the photochopper so that

the motor is operating

the fence extends further into the

low on the motor shaft.

 

optocoupler slots.

 

 

 

 

 

 

A motor bearing has failed

Replace the actuator.

 

 

 

 

There is a loose connection in the

Tighten.

 

screw terminal blocks

 

 

 

 

 

The motor operates in one direction

There is a loose or dirty connection

Clean and tighten.

in the yellow Turck cable

only

 

 

 

The position sensor has failed

Replace the actuator.

 

 

 

 

 

There is a broken motor lead or

Replace the actuator.

 

winding

 

 

 

 

 

 

 

The motor will resume operation

 

The thermal switch has tripped be-

when it cools. This could be caused

 

cause the motor is overheated

by a malfunctioning control panel.

 

 

Consult the factory.

 

 

 

The motor will not move in either

Any of the reasons listed in “The mo-

See above.

direction

tor operates in one direction only”

 

 

The command shaft is jammed

Free the command shaft.

 

 

 

 

Broken gears in the gearmotor

Replace the actuator.

 

 

 

 

Blown relay or fuse.

Check and replace blown relay and/

 

or fuse.

 

 

 

 

 

The motor runs intermittently, sev-

Motor is overheating and the ther-

This could be caused by a malfunc-

tioning control panel. Consult the

eral minutes on, several minutes off

mal switch is tripping

factory.

 

 

 

 

 

 

Bad thermal switch

Replace the actuator.

The motor runs sporadically

 

 

Any of the reasons listed in “The mo-

See above.

 

 

tor will not move in either direction”

 

The motor runs but output shaft will

Stripped gears inside the gear

 

motor or the armature has come un-

Replace the actuator.

not turn

pressed from the armature shaft

 

 

 

6 – 2