6-7 MPS PROBLEM

MPS problems can occur with a status of C Err, R Hi, TGLow. The O2 reading can be 0% to

99%, and probe data will be in the normal ranges. Consider two conditions, A and B.

Refer to Table 6-5to troubleshoot problems with the MPS.

Table 6-5. MPS Troubleshooting

Problem

Cause

Corrective Action

Status is NoGas.

Cell mV is between -20 to 120 mV.

1.Regulator or plumbing fault. The test gas pressure is low for the indicated probe [20 to 25 psig (138 to 172 kPa gage)].

Check test gas pressure [should be 20 psig (138 kPa gage)], regulator, and lines. Reset, repair, or replace the regulator as needed. If only one probe has low flow [less than 5 scfh (2.4 L/min)], check lines, needle valve, connectors, and MPS solenoid for that probe.

2. Test gas low.

Replace empty test gas cylinder with full cylinder. Verify O2 concentration.

3. Wiring fault.

Confirm proper wiring and continuity between MPS and electronics. Repair as needed.

4. Pressure switch fault.

Pressure switch is factory set at 16 psig (68.9 kPa gage). Set test gas regulator pressure to 20 psig (138 kPa gage) to avoid nuisance alarms. Replace faulty switch with a new one if test gas supply is good.

Status is ResHi or CalEr.

Cell mV is between -20 to 120 mV.

The CalEr occurs when the slope calculated from the last calibration was out of range. CalEr can be caused by leaks, a faulty diffusor or sensor cell, erroneous test gas values, or not enough test gas time. Each test gas should be supplied for at least three minutes.

1. Flowmeter set incorrectly.

The flowmeter for each probe must be set individually. Flow should be 5 scfh (2.4 L/min).

2. Wiring fault.

Confirm proper wiring and continuity between MPS and electronics.

3. Piping fault. Faulty gas line or regulator.

Check gas line, valves, and regulators for blockage or corrosion. Repair or replace as needed.

4. Solenoid fault.

Verify nominal 24 VDC at HI GAS, LOW GAS, IN CAL, and CAL RET connections. Voltages should drop to about 4 VDC. If voltage is present but solenoid does not work, replace the solenoid.

5. Termination board fault.

Verify 24 VDC at J11 on termination board. Repair or replace termination board or connectors as needed.

6. Power supply fault.

Verify power supply fuses and output are good and that line voltage is present at J1. Repair or replace the power supply as needed.

7. Power fault.

Check fuses, mains, and circuit breakers. Repair or replace as needed.

6-8 Troubleshooting

Rosemount Analytical Inc. A Division of Emerson Process Management

Page 92
Image 92
Emerson Process Management 3000 MPS Problem, MPS Troubleshooting Problem, Status is NoGas Cell mV is between -20 to 120 mV

3000 specifications

Emerson Process Management is a key player in the field of industrial automation, and one of its flagship offerings is the Emerson Process Management 3000. This system is designed to optimize production processes across a variety of industries, enhancing efficiency and ensuring robust operational performance.

One of the main features of the Emerson Process Management 3000 is its advanced control capabilities. The system employs model predictive control (MPC) technology, which allows for real-time data processing and decision-making. By predicting future trends in process variables, the MPC enables operators to adjust control parameters proactively, minimizing fluctuations and improving overall productivity.

Additionally, the Emerson 3000 integrates seamlessly with existing industrial infrastructure. This system supports a wide range of communication protocols, ensuring compatibility across various devices and sensors. Its flexibility allows companies to leverage their investment in existing technologies while upgrading to more modern control strategies.

The user interface of the Emerson Process Management 3000 is highly intuitive, featuring graphical displays that provide operators with clear visibility into process parameters. This interface is designed for ease of use, with customizable dashboards that can be tailored to meet the specific needs of the users. Training time is significantly reduced due to the straightforward design, leading to quicker onboarding for new operators.

In terms of data analytics, the Emerson 3000 also stands out. It features built-in data logging and trend analysis capabilities, empowering operators to make informed decisions based on historical and real-time data. This analytical strength helps in identifying inefficiencies and potential areas for improvement, contributing to reduced downtime and lower operational costs.

Safety is another critical characteristic of the Emerson Process Management 3000. The system includes robust safety features and compliance with various industry standards. By integrating safety into the control process, it ensures that product quality and equipment integrity are maintained, thus safeguarding both personnel and assets.

Overall, Emerson Process Management 3000 is a sophisticated control system that combines advanced technologies, user-friendly design, and robust safety features. Ideal for industries such as oil and gas, chemicals, and water treatment, it is designed to enhance operational efficiency and drive productivity in modern industrial environments.