Rack Mounting
3-2 Installation
4. InspecttheEnterasysMatrixNSA2G407252foranysignsofphysicaldamage.
ContactEnterasysNetworksifitisdamaged.Referto“GettingHelp”onpage xviii
fordetails.
Rack Mounting
Theinstallationsitemustbewithinreachofthenetworkcablingandmeetthe
requirementslistedbelow:
• Appropriategroundedpowerreceptaclesmustbelocatedwithin7feetofthesite.
•Atemperatureofbetween5°C(41°F)and40°C(104°F)mustbemaintainedatthe
installationsitewithfluctuationsoflessthan10°C(18°F)perhour.
TheEnterasysMatrixNSA2G407252canbemountedinastandard19inchrackwiththe
twoearsprovidedinthecarton.Theprocedureisasfollows:
1. WithfourofthesuppliedM4x6mmflatheadscrews,attachaneartothesideofthe
EnterasysMatrixNSA2G407252asshowninFigure31.Repeattheprocedurefor
theotherear.
Table 3-1 Contents of 2G4072-52
Item
Matrix N Standalone Series 2G4072-52
Accessory Kit including: power cord, rack-mount ears, eight M4 x 6 mm flathead screws, DB9 to
RJ45 converter, and adhesive feet
Installation Guide
Release Notes
Caution: To ensure proper ventilation and prevent overheating, leave a minimum
clearance space of 5.1 cm (2.0 in.) at the left, right, and rear of the device.
Precaución: Para asegurar una buena ventilación y evitar que el sistema se
sobrecaliente, deje un espacio mínimo de 5.1 cm (2 pulgadas) con respecto a los lados y
a la parte posterior del aparato.
Warning: Before rack-mounting the device, ensure that the rack can support it without
compromising stability. Otherwise, personal injury and/or equipment damage may result.
Advertencia. Antes de montar el equipo en el rack, asegurarse que el rack puede
soportar su peso sin comprometer su propia estabilidad, de otra forma, daño personal o
del equipo puede ocurrir.
Warnhinweis: Überzeugen Sie sich vor dem Einbau des Gerätes in das Rack von dessen
Stabilität, ansonsten könnten Personenschäden oder Schäden am Gerät die Folge sein.