Installation and Operation, cont’d

If the events are currently stopped following the momentary (<1 second) press, the Power LED will flash twice indicating the starting of events.

or

If events are currently running following the momentary (<1 second) press, the Power LED will flash three times indicating the stopping of events.

Each flash will last for .25 seconds. Nothing happens if the momentary press does not occur within 1 second.

Mode 4 — Holding the Reset button until the Power LED blinks twice (6 seconds) followed by a momentary (<1 second) press will reset IP settings. The Power LED will blink four times in quick succession, confirming a Mode 4 reset. This mode will

1. Enable ARP program capability.

2. Set IP back to factory IP.

3. Set Subnet back to factory default.

4. Set Gateway back to factory default.

5. Set port mapping back to factory default.

6. Turn DHCP off.

7. Turn events off.

Nothing happens if the momentary press does not occur within one second.

Mode 5 — Holding the Reset button until the Power LED blinks three times (9 seconds) followed by a momentary (<1 second) press will cause an absolute system reset back to factory default conditions. Nothing happens if the momentary press does not occur within 1 second. The power LED will blink four times in quick succession, confirming a Mode 5 reset.

IPL T SF24 and SFI244

Chapter3Three

Connection and Configuration

Connecting the Hardware

Configuring the Hardware