Extron electronic IPL T SF24, SFI244 Series user manual Copyright information, Password information

Models: SFI244 Series IPL T SF24

1 44
Download 44 pages 50.17 Kb
Page 28
Image 28
Login User

Communication and Control, cont’d

X38

= Event data size: b = bit; B = byte (8 bit); S = short (16 bit);

 

L = long (32 bit)

 

 

 

 

This parameter is case sensitive.

 

 

 

 

= Event data to write.

X39

 

=I/O mode: 0 = input; 1 = output; 2 = input plus pull-up resistor;

X40

 

3 = output plus pull-up resistor; 4 = analog in; 5 = analog in w/

 

pull-up; 6 = adjust in (requires

 

 

&

 

thresholds); 7 = adjust

 

X55

X56

 

in w/pull-up (requires

 

&

 

thresholds).

 

&

 

 

 

X55

X56

X55

X56

 

thresholds are not required for modes 0-5.

 

=Setting I/O 0 = off; 1 = on

X42

 

=0 = off; 1 = on; value = 0-4095, based on 12-bit A to D

X43

 

=E-mail recipient number: range = 1 - 64 max

X45

 

=E-mail recipient address: maximum number of characters for a

X46

 

full email address is 31 characters.

 

= Name of e-mail file to be sent: the first line of the file is the

X47

 

subject, the rest is the body of the e-mail.

 

 

 

 

Email files must have the file extension .eml.

 

 

 

 

 

=Event Status fields (8): event_type, event_state, event_paused,

X48

 

error_status, RcvBuff_endptr, UsrBuff_startptr, UsrBuff_endptr

 

=Default Name: Combination of model-name and last 3 pairs of

X49

 

MAC address (e.g., IPL-T-SFI244-00-02-3D)

 

=Redirect: 0 = no redirect; 1-n = redirect serial port from the

X50

 

specified port to allow for a transparent pass-through mode

 

=Connection’s security level: 0 = not logged in; 1 = user;

X52

 

2 = administrator

 

=Timeout for data pass-through mode, after which event data can

X53

 

be inserted into the transmit buffer.

 

=ASCII digit(s) representing numeric value of data element read

X54

 

from event buffer (leading zeros are suppressed)

 

=Upper transition threshold (0 detection = off) for digital inputs;

X55

 

Lower must be smaller than upper (0-4095 based on 12-bit

 

A to D)

X56 =Lower transition threshold (1 detection = on) for digital inputs; Lower must be smaller than upper (0-4095 based on 12-bit

A to D)

The default Web pages will display X55 and X56 in

voltages. (100mV to 24VDC, upper default = 2VDC and lower default = 1VDC). The conversion rate is 162 counts to 1V.

X57 = IR Playback file.

X59 = IR Playback mode: 0 = play once, 1 = play continuously (send IR command again with mode = 0 to stop mode 1 playback)

X60 = IR Learn starting sample # to return (0 = return all data)

X61 = IR Learn ending sample # to return (0 = return all data)

X62 = IR Learn status: 0 = finished, but no IR seen; 1 = finished, buffer overrun; 2 = finished, successful collection; 3 = finished, but aborted; 4 = waiting for first pulse; 5 = busy collecting

X63 = Pulse time in 20MS per count. If parameter is missing or = 0, pulse length = default (25 counts=500MS), max (65536 counts)

X64 = Broadcast repetition rate in seconds (0-256. 0 = disable)

Copyright information

© COPYRIGHT 2003, EXTRON ELECTRONICS IPL T Mxx,

Vx.xx

Thurs, 20 Feb 2003 17:51:04

The copyright message is displayed upon connecting to IP Link product via TCP/IP or Telnet. Mxx is the model and Vx.xx is the firmware version number. The current date and time are displayed. This is followed by a password prompt.

Password information

The “ Password:” prompt requires a password (administrator level or user level) followed by a carriage return. The prompt is repeated if the correct password is not entered.

If the correct password is entered, the unit responds with

Login Administrator ” or “ ”, depending on password entered. If passwords are the same for both administrator and user, the unit will default to administrator privileges.

4-20 IPL T SF24 and IPL T SFI244 • Communication and Control

IPL T SF24 and IPL T SFI244 • Communication and Control 4-21

Page 28
Image 28
Extron electronic IPL T SF24, SFI244 Series user manual Copyright information, Password information