Maintenance – All Motors

Table 44 Preliminary Tests - All Sizes Single- and Three-Phase

“TEST”

PROCEDURE

WHAT IT MEANS

 

1.

Open master breaker and disconnect all leads from control

1.

If the ohms value is normal (table 45), the motor is

 

 

box or pressure switch (QD type control, remove lid) to

 

not grounded and the cable insulation is not damaged.

 

 

avoid electric shock hazard and damage to the meter.

 

 

 

 

 

2.

If the ohms value is below normal, either the windings

Insulation

2.

Use a megohmmeter or set the scale lever to R X 100K

 

are grounded or the cable insulation is damaged.

 

on an Ohmmeter. Zero the meter.

 

Check the cable at the well seal as the insulation is

Resistance

 

 

 

 

 

sometimes damaged by being pinched.

 

 

 

 

 

3.

Connect one meter lead to any one of the motor leads

 

 

 

 

and the other lead to the metal drop pipe. If the drop pipe is

 

 

 

 

plastic, connect the meter lead to ground.

 

 

 

 

 

 

 

 

1.

Open master breaker and disconnect all leads from control

1.

If all ohms values are normal (tables 13, 22, 24 & 26), the

 

 

box or pressure switch (QD type control, remove lid) to

 

motor windings are neither shorted nor open, and the

 

 

avoid electric shock hazard and damage to the meter.

 

cable colors are correct

 

2.

Set the scale lever to R X 1 for values under 10 ohms.

2.

If any one value is less than normal, the motor

 

 

For values over 10 ohms, set the scale lever to R X 10.

 

is shorted.

Winding

 

“Zero” the Ohmmeter.

 

 

 

 

3.

If any one ohm value is greater than normal, the

Resistance

3.

On 3-wire motors measure the resistance of yellow to black

 

winding or the cable is open, or there is a poor cable

 

 

(Main winding) and yellow to red (Start winding).

 

joint or connection.

 

 

On 2-wire motors: measure the resistance from line-to-line.

4.

If some ohms values are greater than normal and some

 

 

 

 

less on single-phase motors, the leads are mixed. See

 

 

Three-phase motors: measure the resistance line-to-line

 

page 46 to verify cable colors.

 

 

for all three combinations.

 

 

 

 

 

 

 

 

 

 

 

ATTACH THIS LEAD

 

 

 

 

 

 

 

 

 

TO WELL CASING OR

 

 

 

 

 

 

 

 

 

DISCHARGE PIPE

 

 

 

 

 

 

L1 L2 R

Y B

 

CONNECT

 

L1 L2 R

Y B

 

 

 

 

THIS LEAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO GROUND

 

 

 

 

 

 

 

RED

 

 

 

 

RED

 

 

 

 

YELLOW

 

 

 

 

YELLOW

 

 

 

 

BLACK

 

 

 

 

BLACK

 

 

TO

GROUND

 

 

 

TO

GROUND

 

 

 

POWER

L1

BLACK

 

 

POWER

L1

 

 

 

SUPPLY {

L2

YELLOW

 

TO

SUPPLY {

L2

BLACK

 

TO

 

 

 

 

 

YELLOW

 

 

 

RED

PUMP

 

 

 

PUMP

 

 

 

{

 

 

 

RED

 

 

GROUND

 

 

 

 

{

 

POWER MUST

 

 

 

POWER MUST

 

GROUND

 

 

 

 

 

 

 

 

 

BE SHUT OFF

 

 

 

 

 

 

 

 

 

 

 

 

BE SHUT OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MEGGER

 

 

OHMMETER

 

 

OR OHMMETER

 

 

 

 

 

 

SET AT R X 1

 

 

SET AT R X 100K

 

 

 

 

 

 

 

 

 

 

FIG. 13

 

 

 

 

FIG. 14

 

 

 

44

Page 53
Image 53
Franklin 2007 manual Preliminary Tests All Sizes Single- and Three-Phase, Resistance