Application – Three-Phase Motors
Three-Phase Motor Lead Identification
WARNING: When installing
Line Connections — Six-Lead Motors
| |
(YELLOW) |
|
| CHECK VALVE OR |
| PIPE PLUG ON RIGHT |
SIDE FACING MOTOR | |
SHAFT | |
(RED) |
|
(BLACK)
(YELLOW)
LEADS LOCATED HERE ONLY FOR 3 LEAD (DOL) MOTORS
90° Lead Spacing
Connections for
L1 |
| L2 |
| L3 | L1 | L2 | L3 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
T1 | T6 | T2 | T4 | T3 | T5 | T1 | T2 | T3 | T4 | T5 | T6 |
U1 | W2 | V1 | U2 | W1 | V2 | U1 | V1 | W1 | U2 | V2 | W2 |
Each motor lead is numbered with two markers, one near each end. To reverse rotation, interchange any two line connections.
Phase Converters
There are a number of different types of phase converters available. Each generates
In all phase converters, the voltage balance is critical to current balance. Although some phase converters may be well balanced at one point on the
at differing points on the curve as water levels and operating pressures fl uctuate. Other converters may be well balanced at varying loads, but their output may vary widely with fl uctuations in the input voltage.
The following guidelines have been established for submersible installations to be warrantable when used with a phase converter.
1.Limit pump loading to rated horsepower. Do not load into motor service factor.
2.Maintain at least 3 ft/s fl ow past the motor. Use a fl ow sleeve when necessary.
3.Use time delay fuses or circuit breakers in pump panel. Standard fuses or circuit breakers do not provide secondary motor protection.
4.SubMonitor may be used with electro mechanical type phase converters, however special connections are required. Consult SubMonitor Manual for connections of receiver and lightning arrestor.
5.SubMonitor will not work with electronic solid state phase converters.
6.Current unbalance must not exceed 10%.
34