Application – Three-Phase Motors

Overload Protection of Three-Phase Submersible Motors Class 10 Protection Required

The characteristics of submersible motors are different than standard motors and special overload protection is required.

If the motor is locked, the overload protection must trip within 10 seconds to protect the motor windings. Subtrol/ SubMonitor, a Franklin-approved adjustable overload relay, or a Franklin-approved fi xed heater must be used.

Fixed heater overloads must be the ambient-compensated quick-trip type to maintain protection at high and low

air temperatures.

All heaters and amp settings shown are based on total line amps. When determining amperage settings or making heater selections for a six-lead motor with a Wye-Delta starter, divide motor amps by 1.732.

pages 28, 29 and 30 list the correct selection and settings for some manufacturers. Approval for other manufacturers’ types not listed may be requested by calling Franklin’s Submersible Service Hotline at 800-348-2420.

Refer to notes on page 29.

Table 28 - 60 Hz 4" Motors

HP

KW

1/2

0.37

3/4

0.55

1

0.75

1.51.1

21.5

32.2

53.7

7.55.5

10 7.5

 

NEMA

HEATERS FOR

ADJUSTABLE

 

OVERLOAD RELAYS

RELAYS

VOLTS

STARTER

FURNAS

G.E.

(NOTE 3)

 

SIZE

 

 

 

 

(NOTE 1)

(NOTE 2)

SET

MAX.

 

 

200

00

K31

L380A

3.2

3.4

230

00

K28

L343A

2.7

2.9

380

00

K22

L211A

1.7

1.8

460

00

-

L174A

1.4

1.5

575

00

-

-

1.2

1.3

200

00

K34

L51CA

4.1

4.4

230

00

K32

L420A

3.5

3.8

380

00

K27

L282A

2.3

2.5

460

00

K23

L211A

1.8

1.9

575

00

K21

L193A

1.5

1.6

200

00

K37

L618A

5.0

5.4

230

00

K36

L561A

4.4

4.7

380

00

K28

L310A

2.6

2.8

460

00

K26

L282A

2.2

2.4

575

00

K23

L211A

1.8

1.9

200

00

K42

L750A

6.3

6.8

230

00

K39

L680A

5.5

5.9

380

00

K32

L420A

3.3

3.6

460

00

K29

L343A

2.8

3.0

575

00

K26

L282A

2.2

2.4

200

0

K50

L111B

8.6

9.3

230

0

K49

L910A

7.5

8.1

380

0

K36

L561A

4.6

4.9

460

00

K33

L463A

3.8

4.1

575

00

K29

L380A

3.0

3.2

200

0

K55

L147B

11.6

12.5

230

0

K52

L122B

10.1

10.9

380

0

K41

L750A

6.1

6.6

460

0

K37

L618A

5.1

5.5

575

0

K34

L510A

4.1

4.4

200

1

K62

L241B

19.1

20.5

230

1

K61

L199B

16.6

17.8

380

0

K52

L122B

10.0

10.8

460

0

K49

L100B

8.3

8.9

575

0

K42

L825A

6.6

7.1

200

1

K68

L332B

28.4

30.5

230

1

K67

L293B

24.6

26.4

380

1

K58

L181B

14.9

16.0

460

1

K55

L147B

12.3

13.2

575

1

K52

L122B

9.9

10.6

380

1

K62

L241B

19.5

21.0

460

1

K60

L199B

16.1

17.3

575

1

K56

L165B

12.9

13.6

28

Page 31
Image 31
Franklin 2007 manual 60 Hz 4 Motors, Heaters for, Overload Relays, Furnas, Set Max