Franklin 2007 Maintenance Electronic Products, Pumptec-Plus, Unit Appears Dead, Yellow Lights

Models: 2007

1 75
Download 75 pages 1.1 Kb
Page 64
Image 64

Maintenance – Electronic Products

Pumptec-Plus

Pumptec-Plus is a pump/motor protection device designed to work on any 230 V single-phase induction motor (PSC, CSCR, CSIR, and split phase) ranging in size from 1/2 to 5 horsepower. Pumptec-Plus uses a micro-computer to continuously monitor motor power and line voltage to provide protection against dry well, water logged tank, high and low voltage and mud or sand clogging.

Pumptec-Plus – Troubleshooting During Installation

SYMPTOM

POSSIBLE CAUSE

SOLUTION

Unit Appears Dead

 

Check wiring. Power supply voltage should be applied to L1 and L2 terminals of the

No Power to Unit

Pumptec-Plus. In some installations the pressure switch or other control devices is wired

(No Lights)

 

to the input of the Pumptec-Plus. Make sure this switch is closed.

 

 

 

 

 

 

 

Pumptec-Plus is calibrated at the factory so that it will overload on most pump systems

 

Unit Needs to Be Calibrated

when the unit is fi rst installed. This overload condition is a reminder that the Pumptec-

Flashing Yellow Light

 

Plus unit requires calibration before use. See step 7 of the installation instructions.

 

 

 

Miscalibrated

Pumptec-Plus should be calibrated on a full recovery well with the maximum water fl ow.

 

Flow restrictors are not recommended.

 

 

 

 

 

 

 

Step C of the calibration instructions indicate that a fl ashing green light condition will

Flashing Yellow Light

2-Wire Motor

occur 2 to 3 seconds after taking the SNAPSHOT of the motor load. On some two wire

During Calibration

motors the yellow light will fl ash instead of the green light. Press and release the reset

 

 

 

button. The green should start fl ashing.

 

 

 

 

 

During the installation of Pumptec-Plus power may be switched on and off several times.

 

Power Interruption

If power is cycled more than four times within a minute Pumptec-Plus will trip on rapid

Flashing Red and

 

cycle. Press and release the reset button to restart the unit.

 

 

Yellow Lights

 

A bobbing fl oat switch may cause the unit to detect a rapid cycle condition on any motor

 

 

 

Float Switch

or an overload condition on two wire motors. Try to reduce water splashing or use a

 

 

different switch.

 

 

 

 

High Line Voltage

The line voltage is over 253 volts. Check line voltage. Report high line voltage to the

 

power company.

 

 

Flashing Red Light

 

 

 

If you are using a generator the line voltage may become too high when the generator

 

Unloaded Generator

unloads. Pumptec-Plus will not allow the motor to turn on again until the line voltage

 

returns to normal. Over voltage trips will also occur if line frequency drops too far

 

 

 

 

below 60 Hz.

 

 

 

 

Low Line Voltage

The line voltage is below 207 volts. Check line voltage.

 

 

 

 

Loose Connections

Check for loose connections which may cause voltage drops.

Solid Red Light

 

 

 

If you are using a generator the line voltage may become too low when the generator

 

 

 

Loaded Generator

loads. Pumptec-Plus will trip on undervoltage if the generator voltage drops below 207

 

volts for more than 2.5 seconds. Undervoltage trips will also occur if the line frequency

 

 

 

 

rises too far above 60 Hz.

 

 

 

55

Page 64
Image 64
Franklin 2007 Maintenance Electronic Products, Pumptec-Plus Troubleshooting During Installation, Unit Appears Dead