Application – Three-Phase Motors
SubMonitor Three-Phase Protection
Applications
SubMonitor is designed to protect
Protects Against
• Under/Overload
• Under/Overvoltage
• Current Unbalance
• Overheated Motor
(if equipped with Subtrol Heat Sensor)
• False Start (Chattering)
• Phase Reversal
Power Factor Correction
In some installations, power supply limitations make it | Table 31 kVAR Required 60 Hz |
| |||||
necessary or desirable to increase the power factor of a |
|
|
|
|
|
| |
| MOTOR |
| KVAR REQUIRED FOR PF OF: | ||||
submersible motor. The table lists the capacitive kVAR |
|
| |||||
HP | KW | 0.90 | 0.95 | 1.00 | |||
required to increase the power factor of large Franklin | |||||||
5 | 3.7 | 1.2 |
| 2.1 | 4.0 | ||
values shown at maximum input loading. | 7.5 | 5.5 | 1.7 |
| 3.1 | 6.0 | |
Capacitors must be connected on the line side of the | 10 | 7.5 | 1.5 |
| 3.3 | 7.0 | |
15 | 11 | 2.2 |
| 4.7 | 10.0 | ||
overload relay, or overload protection will be lost. |
| ||||||
20 | 15 | 1.7 |
| 5.0 | 12.0 | ||
|
| ||||||
| 25 | 18.5 | 2.1 |
| 6.2 | 15.0 | |
| 30 | 22 | 2.5 |
| 7.4 | 18.0 | |
| 40 | 30 | 4.5 |
| 11.0 | 24.0 | |
| 50 | 37 | 7.1 |
| 15.0 | 32.0 | |
| 60 | 45 | 8.4 |
| 18.0 | 38.0 | |
| 75 | 55 | 6.3 |
| 18.0 | 43.0 | |
| 100 | 75 | 11.0 |
| 27.0 | 60.0 | |
| 125 | 90 | 17.0 |
| 36.0 | 77.0 | |
| 150 | 110 | 20.0 |
| 42.0 | 90.0 | |
| 175 | 130 | 9.6 |
| 36.0 | 93.0 | |
| 200 | 150 | 16.0 |
| 46.0 | 110.0 |
Values listed are total required (not per phase).
31