Subtrol-Plus - Troubleshooting After Installation (Continued)
SYMPTOM
POSSIBLE CAUSE OR SOLUTION
| Whenever the pump is off as a result of | |
| A steady light indicates the | |
Tripped Light On | and a fl ashing light indicates repeated trips, requiring manual reset before the pump can be restarted. | |
| Any other red light operation indicates a faulty receiver. | |
| light on. | |
|
| |
Control Circuit | With power turned off, check for a shorted contactor coil or a grounded control circuit lead. The | |
coil resistance should be at least 10 ohms and the circuit resistance to panel frame over 1 megohm. | ||
Fuse Blows | ||
A standard or | ||
| ||
|
| |
| If proper voltage is at the control coil terminals when controls are operated to turn the pump on, but | |
| the contactor does not close, turn off power and replace the coil. If there is no voltage at the coil, | |
| trace the control circuit to determine if the fault is in the | |
| operating switches. This tracing can be done by fi rst connecting a voltmeter at the coil terminals, | |
Contactor Will | and then moving the meter connections step by step along each circuit to the power source, to | |
determine at which component the voltage is lost. | ||
Not Close | ||
| ||
| With the | |
| and with an Ohmmeter set at RX10, measure the resistance between the control terminals. It should | |
| measure 100 to 400 ohms. Depress and hold in the reset button. The resistance between the | |
| control terminals should measure close to infi nity. | |
|
| |
| Check that coil voltage is within 10% of rated voltage. If voltage is correct and matches line voltage, | |
Contactor Hums or Chatters | turn off power and remove the contactor magnetic assembly and check for wear, corrosion, and dirt. | |
If voltage is erratic or lower than line voltage, trace the control circuit for faults similar to the previous | ||
| ||
| item, but looking for a major drop in voltage rather than its complete loss. | |
|
| |
Contactor Opens When Start | Check that the small interlocks switch on the side of the contactor closes when the contactor | |
closes. If the switch or circuit is open, the contactor will not stay closed when the selector switch | ||
Switch is Released | ||
is in HAND position. | ||
| ||
|
| |
Contactor Closes But | Turn off power. Check the contactor contacts for dirt, corrosion, and proper closing when the | |
Motor Doesn’t Run | contactor is closed by hand. | |
|
| |
| With the | |
Signal Circuit Terminals | terminals, with an Ohmmeter set at RX10, measure the resistance between the Signal | |
Do Not Energize | terminals. Resistance should measure close to infi nite. Depress and hold in the reset button. | |
| The resistance between the Signal terminals should measure 100 to 400 ohms. | |
|
|