Communications

PLC/CPU Connection

Symptom

Possible Causes

Solution

 

 

 

CIMPLICITY does not

The system is attempting to

1. With the PLC powered up and

communicate with a PLC that has

communicate with a 90-30 PLC

connected to the Display Station,

been autoconfigured

using the SNP driver and a

establish communication between

(AUTOCONFIG/DEFAULT/I/O

CIMPLICITY project.

the Display Station and PLC via

error).

 

the 90-30 SNP driver.

 

 

2. Using a Hand-Held

 

 

Programmer, toggle the Default

 

 

I/O (Enable or Disable)

 

 

configuration parameter for the

 

 

CPU. Communications between

 

 

the Display Station and the PLC

 

 

will be stopped. (Communications

 

 

are stopped when you toggle from

 

 

Enable to Disable, or vice versa.)

 

 

3. Power cycle the PLC.

 

 

 

Communications between the host

COM port not configured in

Verify that the COM port is

computer and the controller are

system.

configured in the system.

unsuccessful.

 

 

 

 

 

 

Cabling between computer and

Verify that the cable between the

 

controller.

computer and the controller is

 

 

correctly wired.

 

 

 

 

Baud rate and parity configured

Verify that the baud rate and

 

incorrectly.

parity on the computer are

 

 

consistent with those on the

 

 

controller.

 

 

 

 

Wrong address.

Verify that the slave address is

 

 

correct.

 

 

 