MODBUS RTU Communications

Symptom

Possible Causes

Solution

 

 

 

Communications between the host

COM port not configured in

Verify that the COM port is

computer and the controller are

system.

configured in the system.

unsuccessful.

 

 

 

 

 

 

Cabling between computer and

Verify that the cable between the

 

controller.

computer and the controller is

 

 

correctly wired.

 

 

 

 

Baud rate and parity configured

Verify that the baud rate and

 

incorrectly.

parity on the computer are

 

 

consistent with those on the

 

 

controller.

 

 

 

 

MODBUS port not configured for

Verify that the controller's

 

RTU communications.

MODBUS port is configured for

 

 

RTU communications.

 

 

 

 

Wrong address.

Verify that the slave address is

 

 

correct.

 

 

 

Network Communications

Symptom

Possible Causes

Solution

 

 

 

Conflicts on network.

IP Address not unique.

Change the IP address to a unique

 

 

address. (Contact your system

 

 

administrator if this or other

 

 

settings need to be changed.)

 

 

 