!WARNING!
To ensure the safe operation of the TransPort,
you must install and operate it as described in
this manual. In addition, be sure to follow all
applicable safety codes and regulations for
installing electrical equipment in your area.

Transducer Connections

The transducer cables connect to the TransPort with LEMO®
coaxial type connectors. Each color-coded cable has a collar
labeled UPSTREAM or DOWNSTREAM. Make transducer
cable connections to the top of the flowmeter as shown in Figure
2-2 on the previous page. Transducer installation is discussed
separately in Chapter 3.

Analog Input/Output Connections

The TransPort provides one 0/4-20 mA current output and two
4 to 20-mA analog inputs with switchable 16-V supply for
loop- powered temperature transmitters. Connect the inputs/
outputs using a LEMO® multi-pin connector as shown in Figure
2-2 on the previous page. The pin numbers for the connector and
the color code for the standard input/output cable are shown in
Table 2-1 on the next page.