Programming Site Data 4-23
April 2004
Entering Mass Flow Parameters (cont.)
2. If you have enabled Mass Flow, the next prompt asks for the
calculation method. Three options are available: static density,
saturated steam, and steam.
a. Press [ENTER] to open the drop-down menu.
b. Scroll to the appropriate method for your application.
c. Press [ENTER] to confirm the entry.
•If you select Saturated Steam:
The prompt asks for the Saturated Steam input. Press
[ENTER], scroll to either Temperature or Pressure, and
press [ENTER].
•If you select StaticDensity:
The prompt asks for the Static Density value. Press
[ENTER] to open the text box, enter the appropriate value,
and press [ENTER] to confirm the entry.
Pressing the [S] key returns the meter to the Mass Flow prompt,
and then to the Mass Flow tab.
•To confirm the entries and return to Operate mode, press [F3]
(OK).
•To leav e the window without confirming the entries and return
to Operate mode, press [F2] (Cancel) or the [ESC] key.