9

FAN #

1

 

2

 

3

 

4

 

5

 

6

 

 

 

-

+

-

+

-

+

-

+

-

+

-

+

RESULT

Error Message

Fan # Housing High Temperature

 

J5-12

J1-7

 

J5-12

J1-8

 

J5-12

J2-7

 

J5-12

J2-8

 

J5-12

J3-7

 

J5-12

J3-8

12VDC

Burner # Vapor High Temperature

 

J5-12

J1-5

 

J5-12

J1-6

 

J5-12

J2-5

 

J5-12

J2-6

 

J5-12

J3-5

 

J5-12

J3-6

12VDC

Burner # Flame not Detected

 

J5-12

J1-9

 

J5-12

J1-10

 

J5-12

J2-9

 

J5-12

J2-10

 

J5-12

J3-9

 

J5-12

J3-10

12VDC

Plenum # High Temperature

 

J5-12

J1-11

 

J5-12

J1-12

 

J5-12

J2-11

 

J5-12

J2-12

 

J5-12

J3-11

 

J5-12

J3-12

12VDC

Burner # Shutdown Loss of Airflow

 

J5-12

J1-13

 

J5-12

J1-14

 

J5-12

J2-13

 

J5-12

J2-14

 

J5-12

J3-13

 

J5-12

J3-14

Note 1

Fan # Failure No Airflow

 

J5-12

J1-13

 

J5-12

J1-14

 

J5-12

J2-13

 

J5-12

J2-14

 

J5-12

J3-13

 

J5-12

J3-14

Note 2

Fan # cannot Start Check Air Switch

 

J5-12

J1-13

 

J5-12

J1-14

 

J5-12

J2-13

 

J5-12

J2-14

 

J5-12

J3-13

 

J5-12

J3-14

Note 3

Lower or Left Fixed Grain

1100/1200/1300

2200/2300/2400

3300/3400/3600

 

J5-12

J1-19

 

 

J5-12

J1-19

 

 

J5-12

J1-19

 

Lower Adjustable or Right Fixed Grain

 

J5-12

J4-19

 

 

J5-12

J4-19

 

 

J5-12

J4-19

 

Middle Fixed Grain

 

J5-12

N/A

 

 

J5-12

N/A

 

 

J5-12

J4-4

 

Middle Adjustable Grain

 

J5-12

N/A

 

 

J5-12

N/A

 

 

J5-12

J4-8

 

Upper Fixed Grain

 

J5-12

N/A

 

 

J5-12

J4-4

 

 

J5-12

J4-2

 

Upper Adjustable Grain

 

J5-12

N/A

 

 

J5-12

J4-8

 

 

J5-12

J4-6

 

Misc Errors

 

 

 

 

Auxilliary Safety Shutdown

J5-12

J1-20

Note:

 

Motor Overload

J5-12

J4-12

1

This error will occur if the fan and burner were both operating and

Grain Discharge Warning

J5-12

J5-5

 

the air switch opens which indicates loss of static pressure.

Maxon Valve Shut Warning

J5-12

J5-2

 

12 volts should be present if the fan is on.

Unknown Safety Error

J5-12

J5-10

2

This error will occur if after the fan has started the air switch does

20 Second Safety Circuit Failure

J5-12

J5-6

 

not detect any static pressure. 12 volts should be present if

 

 

 

 

the fan is on.

 

 

 

3

The condition for this error will occur if the air switch is stuck

 

 

 

 

in the closed postition. No voltage should be present if the

 

 

 

 

dryer is stopped.

Safety Voltage Check Points

Portable Dryer Troubleshooting

Wiring Reference

Page 10
Image 10
GSI Outdoors PNEG-630 manual Safety Voltage Check Points, Fan #