102

Competitor

 

TRANSFORMER

FUSE

 

 

MONITORING

J5

 

DISPLAY

 

1

 

 

 

 

 

 

 

 

 

RS485 COM PORTS

 

 

 

J7

4

 

J1

1

 

J6

 

 

 

3

 

 

2019

FLAME PROBE A

 

 

 

 

2 N

FLAME PROBE B

J2

J8

1 110VAC IN

1

12VDC NEGATIVE

- 18

17

+ 12VDC OUTPUT

 

3

RL1 N.O.

3

4

+ 12VDC OUTPUT

16

15

+ 12VDC OUTPUT

 

 

RL1 COMMON

5

6

GRAIN TEMP SENSOR

14

13 -

TEMP SENSOR (GROUND)

 

IGN TRAN NEUTRAL

N7

8

PLENUM TEMP SENSOR

12

11

N/C AIRSWITCH (5 VDC)

RL3 N.O. SCR DRIVE OUT

9

10

AIRSWITCH COM (DC NEG)

- 10

9

N/O AIRSWITCH (5 VDC)

 

 

RL3 COM SCR IN

11

12

STOP SWITCH

 

 

+12VDC OUTPUT

8

7

OUT OF GRAIN SWITCH

 

MAIN SOL NEUTRAL

N13

14

START SWITCH

6

5

 

CYCLE SOL NEUTRAL

N15

16

MOTOR OVERLOAD

4

3

REAR DISCHARGE SWITCH

 

 

AC NEUTRAL

N17

18 N

1

GRAIN/PLENUM HIGH LIMIT SWITCH

 

 

HOUSING HI-LIM

2

 

 

LOAD COIL NEUTRAL

N19

20

-

12 VDC GROUND

N

110V NEUTRAL

+12V DC

AC NEUTRAL INPUT RL1 N.C.

IGN TRANS PWR 120VAC NO CONNECTION

RL3 N.C.

MAIN SOL PWR 120VAC CYCLE SOL PWR 120VAC 120VAC TO I/O BOARD

LIGHT AC NEUTRAL SPARE AC OUTPUT

Grain

Wiring Reference

 

11.0 ON A

 

20K SCALE

 

AT 70 DEGREES

USING OHM METER BEGIN CHECKING

IF OHMS DOES NOT = 11.0 K

THE SENSORS FOLLOWING FIG.1

CHECK LOWER AND UPPER TERMINAL

 

STRIP (J7-13 GND & J7-14)

FIG.1

See page 47 for resistance vs.

Temperature chart

IF MEASUREMENTS DO NOT = 11.0 K

IF NONE OF THE MEASUREMENTS = 11.0 K,

CHECK CONNECTIONS IN WHITE

THEN CHECK EACH INDIVIDUAL SENSOR.

JUNCTION BOX ON FAR LEFT AND

 

RIGHT SIDES FACING THE FAN END.

SENSORS COMP98.PRT

Sensor Testing

Portable Dryer Troubleshooting

Page 103
Image 103
GSI Outdoors PNEG-630 manual Grain, Sensor Testing, 102