Portable Dryer Troubleshooting

Wiring Reference

 

 

Meter Roll Reversing

YOU MUST ENTER INTO THE DRYER

PARMETER MODE BY PRESSING THE

INCREASE AND DECREASE BUTTONS

SIMULTANIOUSLY. YOU WILL HAVE

THE FOLLOWING OPTIONS LISTED:

SHUTDOWN HISTORY (PRESS ENTER)

DRYER MODEL # (IE. 1112)

FAN DELAY

(DEFAULT = 5)

FILL AUGER

(DEFAULT = END)

BPH FACTOR

(DEFAULT = 1.0)

TEST METER ROLL (DEFAULT = YES)

TEST AIR SWITCH (DEFAULT = YES)

M.R. REVERSE

(DEFAULT = NO) <- CHANGE TO YES

*REVERSE DELAY (DEFAULT = 60)

*REVERSE TIME (DEFAULT = 1)

*DISPLAYED ONLY IF M.R. REVERSE IS CHANGED TO YES

REVERSE DELAY = METER ROLLS NORMAL ROTATION TIME (AMOUNT OF TIME METER ROLLS WILL OPERATE BEFORE THEY WILL BEGIN REVERSE ROTATION)

REVERSE TIME = METER ROLLS REVERSE ROTATION TIME (AMOUNT OF TIME METER ROLLS WILL OPERATE IN THE REVERSED ROTATION MODE)

EXAMPLE: REVERSE DELAY = 10 MINUTES REVERSE TIME = 1 MINUTE

NOTE:

WHEN INSTALLING RELAY

BASE NOTE POSITION OF

SLOTS FOR RELAY!!

TO

SCR DRIVE

BOARD

A+ A-

ORANGE

 

PURPLE

 

 

 

85

41

JUMPER WIRES SHOULD

GO BETWEEN:

TERMINALS 4 AND 5

TERMINALS 1 AND 8

LOCATE THE ORANGE AND

PURPLE WIRES COMING FROM

THE SCR DRIVE BOARD GOING

TO THE TERMINAL STRIP AND

INSERT THE RELAY AS SHOWN

 

 

BLACK

14

13

WHITE

 

 

 

 

 

 

12

9

 

 

 

 

 

 

 

 

 

 

 

J7-17

 

 

 

 

J8-20

(110 VAC CONTROL)

 

 

 

 

(110 VAC NEUTRAL)

 

 

PURPLE

 

 

ORANGE

 

 

 

 

 

 

 

 

IMPORTANT

 

 

 

 

 

 

 

 

YOU MUST ADD A JUMPER WIRE

 

 

 

 

 

 

 

FROM J9-09 TO J7-16 IN THE

 

A- TO

A+

 

 

LOWER CONTROL BOX.

 

 

 

 

 

 

 

DC DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR

 

 

 

 

37

Page 38
Image 38
GSI Outdoors PNEG-630 manual Meter Roll Reversing, Default = END