WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
•ALWAYS maintain specified clearances around venting and firestop systems.
•Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
Top Vent - Horizontal Termination
Venting with 1 elbow
V1 Minimum | H1 Maximum | ||
1 ft. | 305 mm | 2 ft. | 610 mm |
2 ft. | 610 mm | 6 ft. | 1829 |
3 ft. | 914 mm | 9 ft. | 2743 |
4 ft. | 1219 mm | 12 ft. | 3658 |
5 ft. | 1524 mm | 15 ft. | 4572 |
6 ft. | 1829 mm | 18 ft. | 5486 |
7 ft. | 2134 mm | 21 ft. | 6401 |
8 ft. | 2438 mm | 24 ft. | 7315 |
V1 + H1 = 63 ft. (19.2 m) Maximum
Note: 12 inches minimum vertical is required prior to attaching any elbow to the appliance.
Note: Use DVP Series components only.
H1
V1
Figure 7.4
Heat & Glo • RED40, RED40ST • | 25 |
|