Top Vent - Vertical Termination

Top Vent - Vertical Termination

No Elbows

V = 3 ft Min. (1m), 50 ft. Max. (15.2 m)

Note: If installing a vertical vent/termination off the top of the appliance, the optional exhaust restrictor may be needed.

Note: Use DVP Series

components only.

V

Figure 7.7 Vertical Vent Maximum

Exhaust restrictors are recommended for these vertically terminated products which have excessive draft. Exhaust restrictors will compensate for high draft, and restore vi- sual flame height. If the vent configuration has a total ver- tical of 20-50 feet, an exhaust restrictor may be needed. The exhaust restrictor can be located in the appliance manual bag.

Exhaust restrictor Instructions

1.Locate the two pilot holes in the inside firebox cham- ber as shown in Figure 7.8.

2.Center the exhaust restrictor such that the thru holes in the vent restrictor align with the pilot holes in the inner firebox chamber.

3.Use two 1/2 inch self-piercing screws to secure vent restrictor to firebox heat shield. See Figure 7.8.

EXHAUST RESTRICTOR

Figure 7.8 Exhaust Restrictor

4.In some applications, such as those where the fire- place is elevated off the floor, the vent restrictor may be painted, but painting is not required.

5.Recommended restrictor usage: 20 to 30 ft. = 4 inch restrictor 30 ft. and up = 3 inch restrictor

NOTICE: Before painting, contact your dealer for information on the appropriate high temperature paint.

28

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

Page 28
Image 28