Heat & Glo LifeStyle RED40ST owner manual Non-CombustibleFinish Materials, 7 Overlap Fit Method

Models: RED40ST RED40

1 82
Download 82 pages 42.72 Kb
Page 56
Image 56
Non-Combustible Finish Materials

WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation of doors and louvers.

WARNING! Risk of Fire! DO NOT install drywall or other combustible materials directly onto the factory- installed non-combustible board. Overlapping materials could ignite.

Decorative facing material thickness is measured from the face of the factory-installed non-combustible board. See Figure 13.5 and Figure 13.6.

The mesh front can be installed such that it overlaps non-combustible materials up to 1 in. thick. See Figure 13.7and Figure 13.8.

Refer to Section 1.E and 1.F of this manual for definition and qualifications and definition of non-combustible and combustible materials.

Specific requirements for each method if installation are described below and on the following pages of this section.

Non-Combustible Finish Materials

0 - 1 inch thickness-Overlap Fit Method

The mesh front is designed to overlap finish materials 0 inches to 1 inch thick. See Figure 13.7.

NOTICE: This one inch maximum not only includes the decorative finish materials (marble, tile, slate, etc) but also the thin set, lath and adhesive used to attach the decorative finish material.

The non-combustible finish material can be installed up to the 16 inch (height) by 43 inch (width) fireplace opening.

 

33-1/2 IN. HEIGHT

 

FACTORY INSTALLED

 

NON-COMBUSTIBLE BOARD

SIDE FINISH NON-COMBUSTIBLE

 

BOARD (2)

 

47 IN. WIDTH

 

FACTORY INSTALLED NON-COMBUSTIBLE BOARD

= NO SCREWS IN THIS AREA

= 2 IN. MAX. SCREW LENGTH

Figure 13.8 Non-Combustible Finish Material Diagram for 0-1 Inch Thick Overlap Fit Method

11-1/4 IN.

 

3-1/2 IN.

 

3-1/2 IN.

 

 

COMBUSTIBLE

 

FRAMING

 

1/2 IN. THICK

 

WALL SHEATHING

7-1/4 IN.

 

1/2 IN.

20-3/4 IN.

 

FACTORY-SUPPLIED

 

NON-COMBUSTIBLE

 

BOARD

1 IN.

 

 

NON-COMBUSTIBLE BOARD

 

ON FRONT FACE (SIDE VIEW)

 

= AIR SPACE

Figure 13.7 Overlap Fit Method

56

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

Page 56
Image 56
Heat & Glo LifeStyle RED40ST Non-CombustibleFinish Materials, 0 - 1 inch thickness-OverlapFit Method, 7 Overlap Fit Method