Defrost Control

"Defrost operation is controlled by timer and sensing temperature of outdoor pipe.

"The first defrost starts only when the outdoor pipe temperature falls below 21°F after 60 minutes passed from starting of heating operation and more than 10 minutes operation of compressor.

"Defrost ends after 12 minutes passed from starting of defrost operation or when the outdoor fan operates with- in 4 minutes after the outdoor pipe temperature rises over WF even if before 12 minutes.

"The second defrost starts only when the outdoor pipe temperature falls below 21°F after 60 minutes passed from ending of the first defrost and more than 10 minutes operation of compressor.

OUTDOOR

More than 60 minutes of

Within

More than 60 minutes of

Defrost

PIPE TEMP.

heating operation

12minutes

heating operation

 

More than 10 min.

Defrost

More than 10 min.

 

540F

running of compressor

 

running of compressor

 

 

 

 

 

(DEFROST OFF)

 

 

 

 

21°F

 

 

 

 

(DEFROST ON)

 

 

 

 

 

 

Within

HOT-

 

 

 

4 minute

START

 

INDOOR FAN SPEED

ON

OFF

ON

OFF

COMPRESSOR

ON

ON

ON

ON

4-WAY VALVE

ON

OFF

ON

OFF

OUTDOOR FAN

ON

OFF

ON

OFF

-19-

"

Page 19
Image 19
Heat Controller MSS-024B/A Rý u, Pipe Temp, Defrost OFF, Defrost on, Indoor FAN Speed OFF Compressor WAY Valve Outdoor FAN