"Cycle Troubleshooting Guide

1. Trouble analysis

1. Check temperature difference between intake and discharge air and operating current.

Temp. difference

:approx. 0°F

All amount of refrigerant leaked

Current

:less than 80% of

out.

 

rated current

Check refrigeration cycle.

Temp. Difference

Temp. difference

Current

Operating Current

Temp. difference

Current

:approx. a°C(140F) I

Refrigerant leakage

:less than 80%

of

Clog of refrigeration cycle

rated current

 

Defective compressor

:less than 80C(1 40F)

 

-less than 80%

of

Excessive amount of refrigerant

rated current

 

 

Temp.difference :over8°C(14°F) Normal

Notice:

Temperature difference between intake and discharge air depends on room air humidity. When the room air

"humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure

Temperature

Cause of Trouble

(Compared with the

(Compared with the

normal value)

normal value)

 

 

High

Defective compressor

 

Defective 4-way reversing valve

Higher

 

 

 

 

Normal

Excessive amount of refrigerant

 

 

Insufficient amount of

Lower

Higher

reidgerant(Leakage)

 

 

Clogging

Description

Current is low.

High pressure does not quickly rise at the beginning of operation.

Current is low.

Current is low.

Notice:

1.The suction pressure is usually 56.8-71.0 PSIG at normal condition.

2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty-

-49-