Heat Controller MSS-012B/A, MSH-0186/A Selection of the best location, Roof Top Installations

Models: MSH-01 2B/A MSH-024B/A MSS-024B/A MSH-0186/A MSS-018B/A MSS-009B/A MSS-012B/A

1 86
Download 86 pages 29.35 Kb
Page 25
Image 25

"(1) Installation Parts Provided

-------------- - - - --

1. Type "A' screw

 

 

3. Type '13' screw

_ 4

 

s.. .r

 

 

a_-p

4. Holder Remote-Controller

'_

2. Installation Plate

$

(2)Installation of Indoor, Outdoor unit

1)Selection of the best location

1. Indoor unit.

-There should not be any heat source or steam near the unit.

" There should not be any obstacles to prevent the air circulation.

" A place where air circulation in the room will be good. " A place where drainage can be easily obtained.

" A place where noise prevention is taken into consideration.

" Do not install the unit near the door way.

" Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

2. Outdoor unit

" if an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat

"

radiation from the condenser is not restricted.

" There should not be any animals or plants which could be affected by hot air discharged.

" Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

Roof Top Installations

lt it is necessary to instal units on a roof structure, be sure to elevate aril level the units. Ensure the roof

structure and anchoring method are adequate for unit location. Consult local codes regarding rooftop mounting.

NOTE; When condensing unit is to be installed on a

bonded guuaranlted roof, a release must be obtained

 

from the building owner to free the installer from all

Indoor unit

liabilities.

 

 

 

 

 

 

 

 

 

3. Piping length and the elevation

 

 

MODEL

Pipe Size

Max.

Max.

A

 

(Cooling Cape.)

GAS

LIQUID

length

Elevation

B

 

A

B

Outdoor unit

9k, 12k

1/2'

1/4'

15m(Saft)

Bm(26ft)

 

18k, 24k

518'

3/8'

15m(50ft)

8m(26ft)

 

 

 

 

 

-25-

 

"