" Cooling & Heating Models

INDOOR UNIT

OUTDOOR UNIT

CAPILLARYTUBE f- CHECKVALVE

HEAT

 

EXCHANGER

HEAT

(EVAPORATOR) I / \

EXCHANGER

 

(CONDENSER)

i f

GAS SIDE

REVERSING

VALVE1

----º

COMPRESSOR .- COOLING

.4 -- HEATING

"

MODEL

Pipe size(Diametero)

Piping length

Elevation

Gas

Liquid

Rated

Max

Rated

Max

 

9k, 12k

1/2"

1/4"

7.62m(25ft)

15m(50ft)

5m(16ft)

8m(26tt)

(Camay a Heating)

 

 

 

 

 

 

18k, 24k

5/8"

g/8

7.62m(25ft)

15m(50ft)

Sm(16ft)

8m(26ft)

(CodkV a Heating)

 

 

 

 

 

 

For installation over rated, 'a proper ant"

a proper quantity of refrigerant

9k, 12k

0.2 Oz

18k, 24k

0.3 Oz

of refrigerant should be added for each foot.

Ex) 18K When installed at a distance of 3011t, 1.5 Oz of refrigerant should be added.

(30-25)x 0.302 =1.5 Oz of refrigerant to add

Unit precharged for 25ft. line sets.