"Display Function

Operation Indicator

I

O

 

" Cooling, Soft Dry, Fan, Heating

 

 

Sleep timer Indicator

 

 

 

" Sleep Mode

 

 

 

Timer Indicator

I

0

 

 

 

 

-Timer Mode

 

 

 

Defrost Indicator or

 

 

: Cooling & Heating Model only

 

0

 

Hot start Indicator

 

 

 

OUT

 

 

 

: only Cooling Model

 

 

DOOR

" Hot-start, Defrost

 

 

 

 

 

" Compressor ON

 

 

 

" BUZZER SOUND

 

" Power Input or Reset

: One short beep.

"

" When Operation Stop Button Is pressed

: One tong beep.

"When Remote Controller Buttons except for Operation Stop are pressed : Two short beep.

"When Forced Operation Button is pressed : Two Short beep.

Self-diagnosis Function

CODE NO.

DIAGNOSIS

Operation Indicator LED Blinks

Unit Operation

O

Indoor room temperature thermistor or

Once

Still Operation

pipe temperature thermistor Short/Open

 

 

®

Outdoor pipe thermistor Short/Open

Twice

Outdoor Unit Off

®Communication failure between indoor and

outdoor

5 times

Stop

Indoor fan locked

8 times

stop

"LED blinks as many times as code No. (0.5 second ON/0.5 second OFF) with 3 seconds interval.

"While the unit Is off, no indication displays.

"If more than one code occurs simultaneously, bigger lode No. is displayed.

-23-

"

Page 23
Image 23
Heat Controller MSH-01 2B/A, MSH-0186/A, MSS-018B/A manual Display Function, Self-diagnosis Function, Buzzer Sound, Diagnosis