2.5 Initialization setting
The initialization function allows you to initialize the adjusted settings on the inverter to restore the factory settings. You can also clear the trip history data alone.
The settings of initialization are described below.
The settings of "P100" to "P131",
Item | Function code | Data | Description | |
Initialization mode |
| 00 | Clearing on the trip history data | |
| 01 | Initializing only the settings | ||
(parameters or trip | b084 | The factory settings are restored. | ||
| ||||
history) |
|
|
| |
| 02 | Clearing the trip history data and initializing the | ||
|
| settings | ||
|
|
| ||
Country code for | b085 | 00 | Defaults intended for Japan | |
01 | Defaults intended for Europe | |||
initialization | ||||
| 02 | Defaults intended for the U.S.A. | ||
|
|
(Initializing procedure)
Adjust the above settings as required, and then perform the following procedure:
1) Holding down the FUNC and [2] | 2) Initialization is in progress. | 3) When the initialization is |
(down) keys, press and hold down | - The above figure shows the | completed, the monitor displays |
the STOP/RESET key. | monitor display (indicating that the | code "d001". |
- After the monitor starts blinking, | initialization is in progress) | Confirm that the settings have |
release only the STOP/RESET | intended for Japan. Those | been initialized. |
key. (The display on the monitor | intended for other regions and trip |
|
changes to that shown in the | history clearance are shown |
|
middle figure above. | below. |
|
- Release the FUNC and [2] |
|
|
(down) keys. |
|
|
|
| |
display intended for Europe |
|
|
In the
Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121, C122, and C123) and thermistor coefficient setting (C085).
Note 2: The initialization operation does not initialize the settings of easy sequence user parameters (P100 to P131).
2 - 11