3.2 Function Modes

No.

Function name

Function code

Range of data

5

Function for factory adjustment

C170-C194

Change inhibited

6

Region code for inverter

C195

JP (intended for Japan)

7

Capacity code for inverter

C196

0.2 to 55.0 (kW)

8

Voltage class code for inverter

C197

200 (200 V class) or 400 (400 V class)

9

Inverter mode

C198

00(SJ700)

3.3 How To Reference the Data Area (d105) Corresponding to Trip History

In the data area you can directly reference the factors (determined by the gate array) of the past six trips. Do not change the value set as "C172".

(1)Specify "FFFF" for "C170".

(2)Specify "A56A" for "C171".

(3)Reference the data of "C172". Record the last two digits of the data. (The range of data is "**00" to "**05".)

(4)Specify one of the values listed in the table below for "C171" according to the target trip history data and the value of "C172".

Target

 

 

Value of "C172"

 

 

history

**00

**01

**02

**03

**04

**05

data

 

 

 

 

 

 

d081

A56E

A582

A596

A5AA

A5BE

A5D2

d082

A5D2

A56E

A582

A596

A5AA

A5BE

d083

A5BE

A5D2

A56E

A582

A596

A5AA

d084

A5AA

A5BE

A5D2

A56E

A582

A596

d085

A596

A5AA

A5BE

A5D2

A56E

A582

d086

A582

A596

A5AA

A5BE

A5D2

A56E

Example 1: Referencing the history data of "d083" when "C172" is "**02"

(1)As shown in the above table, the data of "d083" is "A56E" when "C172" is "**02".

(2)Specify "A56E" for "C171".

(5)Reference the value displayed as "C172". The first two digits of the 4-digit value displayed correspond to the value of "d105".

□□□□

Code of the trip factor determined by gate array

Example 2:

When the value of "C172" is "08**", the trip factor is overvoltage protection because bit 3 is "1".

3-2

Page 42
Image 42
Hitachi SJ700-2 Series service manual Function Modes