Name | Description |
| Display on |
| Display on | Troubleshooting and corrective action | |||||
digital operator | remote operator | ||||||||||
|
|
| |||||||||
| If the inverter input voltage drops, the |
|
|
|
|
|
|
|
| Check whether the power supply voltage has | |
| control circuit of the inverter cannot |
|
|
|
|
|
|
|
| ||
| function normally. Therefore, the inverter |
|
|
|
|
|
|
|
| dropped. | |
| shuts off its output when the input |
|
|
|
|
|
|
|
| (Check the power supply.) | |
Undervoltage | voltage falls below a specified level. |
|
|
|
|
|
| Under.V |
| Check whether the power supply capacity is | |
| The inverter will trip if the DC voltage |
|
|
|
|
|
|
|
| sufficient. | |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |||
| across the P and N terminals exceeds |
|
|
|
|
|
|
|
| (Check the power supply.) | |
| about 175 VDC (in case of the 200 V |
|
|
|
|
|
|
|
| Check whether the thyristor has been damaged. | |
| class models) or about 345 VDC (in case |
|
|
|
|
|
|
|
| (Check the thyristor.) | |
| of the 400 V class models). |
|
|
|
|
|
|
|
|
| |
| If an error occurs in the internal current |
|
|
|
|
|
|
|
|
| |
| detector (CT), the inverter will shut off its |
|
|
|
|
|
|
|
| Check whether the inverter has failed. | |
CT error | output and display the error code shown |
|
|
|
|
|
| CT |
| ||
on the right. The inverter will trip when |
|
|
|
|
|
|
| (Repair the inverter.) | |||
|
|
|
|
|
|
|
|
| |||
| the CT outputs about 0.6 V or more at |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
| If the internal CPU malfunctions or an |
|
|
|
|
|
|
|
| Check for the noise sources located near the | |
| error occurs in it, the inverter will shut off |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| inverter. | ||
CPU error | its output and display the error code |
|
|
|
|
|
| CPU |
| (Remove noise sources.) | |
(*3) | shown on the right. |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| Check whether the inverter has failed. | |||
| Note: Reading an abnormal data from |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| (Repair the inverter.) | ||
| the EEPROM may result in a CPU error. |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
| If an error occurs in the external |
|
|
|
|
|
|
|
| Check whether an error has occurred in the | |
| equipment or device connected to the |
|
|
|
|
|
|
|
| external equipment (when the external trip | |
External trip | inverter, the inverter will fetch the error |
|
|
|
|
|
| EXTERNAL |
| function has been enabled). | |
| signal and shut off its output. (This |
|
|
|
|
|
|
|
| (Recover the external equipment from the error.) | |
|
|
|
|
|
|
|
|
| |||
| protective function is enabled when the |
|
|
|
|
|
|
|
|
| |
| external trip function is enabled.) |
|
|
|
|
|
|
|
|
| |
| A USP error is indicated when the |
|
|
|
|
|
|
|
| Check whether the inverter power has been | |
| inverter power is turned on with an input |
|
|
|
|
|
|
|
| turned on with an input operation signal remaining | |
USP error | operation signal remaining in the |
|
|
|
|
|
| USP |
| in the inverter (when the USP function has been | |
inverter. (This protective function is |
|
|
|
|
|
|
| enabled). | |||
|
|
|
|
|
|
|
|
| |||
| enabled when the USP function is |
|
|
|
|
|
|
|
| (Reset the operation command, and then turn on | |
| enabled.) |
|
|
|
|
|
|
|
| the inverter power.) | |
| When the inverter power is turned on, |
|
|
|
|
|
|
|
| Check for the ground fault. | |
| this protective function detects the |
|
|
|
|
|
|
|
| (Check the output cables and motor.) | |
ground fault between the inverter output |
|
|
|
|
|
|
|
| Check the inverter itself for abnormality. | ||
protection | circuit and the motor to protect the |
|
|
|
|
|
| GND.Flt |
| (Remove the output cables from the inverter, and | |
inverter. (This function does not operate |
|
|
|
|
|
|
| then check the inverter.) | |||
(*3) |
|
|
|
|
|
|
|
| |||
when a residual voltage remains in the |
|
|
|
|
|
|
|
| Check the main circuit for abnormality. | ||
|
|
|
|
|
|
|
|
| |||
| motor.) |
|
|
|
|
|
|
|
| (Check the main circuit with reference to | |
|
|
|
|
|
|
|
|
|
| Chapter 6.) (Repair the inverter.) | |
| This protective function determines an |
|
|
|
|
|
|
|
| Check whether the input voltage is high while the | |
| error if the input voltage is kept above |
|
|
|
|
|
|
|
| inverter is stopped. | |
Input | the specification level for 100 seconds |
|
|
|
|
|
|
|
| (Lower the input voltage, suppress the power | |
while the inverter is stopped. |
|
|
|
|
|
|
|
| voltage fluctuation, or connect an AC reactor | ||
|
|
|
|
|
| OV.SRC |
| ||||
overvoltage | The inverter will trip if the DC voltage of |
|
|
|
|
|
|
| between the power supply and the inverter input.) | ||
protection | the main circuit is kept above about 390 |
|
|
|
|
|
|
|
|
| |
| VDC (in case of the 200 V class models) |
|
|
|
|
|
|
|
|
| |
| or about 780 VDC (in case of the 400 V |
|
|
|
|
|
|
|
|
| |
| class models). |
|
|
|
|
|
|
|
|
| |
| If an instantaneous power failure lasts 15 |
|
|
|
|
|
|
|
| Check whether the power supply voltage has | |
| ms or more, the inverter will shut off its |
|
|
|
|
|
|
|
| dropped. | |
Instanta- | output. |
|
|
|
|
|
|
|
| (Recover the power supply.) | |
When the power failure duration is long, |
|
|
|
|
|
|
|
| Check the MCB and magnetic contactors for poor | ||
neous power | the inverter assumes a normal |
|
|
|
|
|
|
| contacts. | ||
failure | If a restart mode has been selected and |
|
|
|
|
|
|
|
| (Replace the MCB and the magnetic contactor.) | |
|
|
|
|
|
|
|
| ||||
protection |
|
|
|
|
|
|
|
| |||
an operation command remains in the |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
| inverter, the inverter will restart after the |
|
|
|
|
|
|
|
|
| |
| power is recovered. |
|
|
|
|
|
|
|
|
| |
Temperature | The inverter will display the error code |
|
|
|
|
|
|
|
| Check whether the cooling efficiency has been | |
error due to | shown on the right if the lowering of |
|
|
|
|
|
|
|
| lowered. | |
low |
|
|
|
|
|
| OH.stFAN |
| (Replace the cooling fan.) | ||
occurrence of the temperature error |
|
|
|
|
|
|
|
| Check the heat sink for clogging. | ||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||||
speed | described below. |
|
|
|
|
|
|
|
| (Clean the heat sink.) | |
Temperature | If the main circuit temperature rises |
|
|
|
|
|
|
|
| Check whether the inverter is installed vertically. | |
because of a high ambient temperature |
|
|
|
|
|
| OH.fin |
| (Check the installation.) | ||
error | or for other reasons, the inverter will shut |
|
|
|
|
|
|
| Check whether the ambient temperature is high. | ||
|
|
|
|
|
|
|
| ||||
| off its output. |
|
|
|
|
|
|
|
| (Lower the ambient temperature.) |