Name

Description

 

Display on

 

Display on

Troubleshooting and corrective action

digital operator

remote operator

 

 

 

 

If the inverter input voltage drops, the

 

 

 

 

 

 

 

 

Check whether the power supply voltage has

 

control circuit of the inverter cannot

 

 

 

 

 

 

 

 

 

function normally. Therefore, the inverter

 

 

 

 

 

 

 

 

dropped.

 

shuts off its output when the input

 

 

 

 

 

 

 

 

(Check the power supply.)

Undervoltage

voltage falls below a specified level.

 

 

 

 

 

 

Under.V

 

Check whether the power supply capacity is

 

The inverter will trip if the DC voltage

 

 

 

 

 

 

 

 

sufficient.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

across the P and N terminals exceeds

 

 

 

 

 

 

 

 

(Check the power supply.)

 

about 175 VDC (in case of the 200 V

 

 

 

 

 

 

 

 

Check whether the thyristor has been damaged.

 

class models) or about 345 VDC (in case

 

 

 

 

 

 

 

 

(Check the thyristor.)

 

of the 400 V class models).

 

 

 

 

 

 

 

 

 

 

If an error occurs in the internal current

 

 

 

 

 

 

 

 

 

 

detector (CT), the inverter will shut off its

 

 

 

 

 

 

 

 

Check whether the inverter has failed.

CT error

output and display the error code shown

 

 

 

 

 

 

CT

 

on the right. The inverter will trip when

 

 

 

 

 

 

 

(Repair the inverter.)

 

 

 

 

 

 

 

 

 

 

the CT outputs about 0.6 V or more at

 

 

 

 

 

 

 

 

 

 

power-on.

 

 

 

 

 

 

 

 

 

 

If the internal CPU malfunctions or an

 

 

 

 

 

 

 

 

Check for the noise sources located near the

 

error occurs in it, the inverter will shut off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter.

CPU error

its output and display the error code

 

 

 

 

 

 

CPU

 

(Remove noise sources.)

(*3)

shown on the right.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the inverter has failed.

 

Note: Reading an abnormal data from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Repair the inverter.)

 

the EEPROM may result in a CPU error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If an error occurs in the external

 

 

 

 

 

 

 

 

Check whether an error has occurred in the

 

equipment or device connected to the

 

 

 

 

 

 

 

 

external equipment (when the external trip

External trip

inverter, the inverter will fetch the error

 

 

 

 

 

 

EXTERNAL

 

function has been enabled).

 

signal and shut off its output. (This

 

 

 

 

 

 

 

 

(Recover the external equipment from the error.)

 

 

 

 

 

 

 

 

 

 

protective function is enabled when the

 

 

 

 

 

 

 

 

 

 

external trip function is enabled.)

 

 

 

 

 

 

 

 

 

 

A USP error is indicated when the

 

 

 

 

 

 

 

 

Check whether the inverter power has been

 

inverter power is turned on with an input

 

 

 

 

 

 

 

 

turned on with an input operation signal remaining

USP error

operation signal remaining in the

 

 

 

 

 

 

USP

 

in the inverter (when the USP function has been

inverter. (This protective function is

 

 

 

 

 

 

 

enabled).

 

 

 

 

 

 

 

 

 

 

enabled when the USP function is

 

 

 

 

 

 

 

 

(Reset the operation command, and then turn on

 

enabled.)

 

 

 

 

 

 

 

 

the inverter power.)

 

When the inverter power is turned on,

 

 

 

 

 

 

 

 

Check for the ground fault.

 

this protective function detects the

 

 

 

 

 

 

 

 

(Check the output cables and motor.)

Ground-fault

ground fault between the inverter output

 

 

 

 

 

 

 

 

Check the inverter itself for abnormality.

protection

circuit and the motor to protect the

 

 

 

 

 

 

GND.Flt

 

(Remove the output cables from the inverter, and

inverter. (This function does not operate

 

 

 

 

 

 

 

then check the inverter.)

(*3)

 

 

 

 

 

 

 

 

when a residual voltage remains in the

 

 

 

 

 

 

 

 

Check the main circuit for abnormality.

 

 

 

 

 

 

 

 

 

 

motor.)

 

 

 

 

 

 

 

 

(Check the main circuit with reference to

 

 

 

 

 

 

 

 

 

 

Chapter 6.) (Repair the inverter.)

 

This protective function determines an

 

 

 

 

 

 

 

 

Check whether the input voltage is high while the

 

error if the input voltage is kept above

 

 

 

 

 

 

 

 

inverter is stopped.

Input

the specification level for 100 seconds

 

 

 

 

 

 

 

 

(Lower the input voltage, suppress the power

while the inverter is stopped.

 

 

 

 

 

 

 

 

voltage fluctuation, or connect an AC reactor

 

 

 

 

 

 

OV.SRC

 

overvoltage

The inverter will trip if the DC voltage of

 

 

 

 

 

 

 

between the power supply and the inverter input.)

protection

the main circuit is kept above about 390

 

 

 

 

 

 

 

 

 

 

VDC (in case of the 200 V class models)

 

 

 

 

 

 

 

 

 

 

or about 780 VDC (in case of the 400 V

 

 

 

 

 

 

 

 

 

 

class models).

 

 

 

 

 

 

 

 

 

 

If an instantaneous power failure lasts 15

 

 

 

 

 

 

 

 

Check whether the power supply voltage has

 

ms or more, the inverter will shut off its

 

 

 

 

 

 

 

 

dropped.

Instanta-

output.

 

 

 

 

 

 

 

 

(Recover the power supply.)

When the power failure duration is long,

 

 

 

 

 

 

 

 

Check the MCB and magnetic contactors for poor

neous power

the inverter assumes a normal power-off.

 

 

 

 

 

 

Inst.P-F

 

contacts.

failure

If a restart mode has been selected and

 

 

 

 

 

 

 

 

(Replace the MCB and the magnetic contactor.)

 

 

 

 

 

 

 

 

protection

 

 

 

 

 

 

 

 

an operation command remains in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter, the inverter will restart after the

 

 

 

 

 

 

 

 

 

 

power is recovered.

 

 

 

 

 

 

 

 

 

Temperature

The inverter will display the error code

 

 

 

 

 

 

 

 

Check whether the cooling efficiency has been

error due to

shown on the right if the lowering of

 

 

 

 

 

 

 

 

lowered.

low

cooling-fan speed is detected at the

 

 

 

 

 

 

OH.stFAN

 

(Replace the cooling fan.)

cooling-fan

occurrence of the temperature error

 

 

 

 

 

 

 

 

Check the heat sink for clogging.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed

described below.

 

 

 

 

 

 

 

 

(Clean the heat sink.)

Temperature

If the main circuit temperature rises

 

 

 

 

 

 

 

 

Check whether the inverter is installed vertically.

because of a high ambient temperature

 

 

 

 

 

 

OH.fin

 

(Check the installation.)

error

or for other reasons, the inverter will shut

 

 

 

 

 

 

 

Check whether the ambient temperature is high.

 

 

 

 

 

 

 

 

 

off its output.

 

 

 

 

 

 

 

 

(Lower the ambient temperature.)

*3 The inverter will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power.