3.4.2Confirming the completion of initialization
(1)Confirm the voltage class setting. (Confirming method)
Display code "A082" on the monitor, press the FUNC key, and then confirm that data shown in the table below is displayed on the monitor.
Note: Initialization switches the display mode of the digital operator to basic mode. Therefore, display code "b037" on the monitor before confirmation, and then select "00".
Inverter model | Value of "b082" |
200 | |
| 400 |
(2)Confirm the capacity setting. (Confirming method)
Display code "H003" on the monitor, press the FUNC key, and then confirm that the set capacity code data is displayed on the monitor. After confirmation, change the value of "b037" back to "04".