Default

 

 

 

Code

Function name

Monitored data or setting

 

 

 

 

 

Note

 

 

 

 

_FF

_FEF

_FUF

 

 

 

 

 

 

 

 

 

 

 

 

b078

Cumulative input power data

Clearance by setting "01" and pressing the STR key

 

 

00

 

 

 

 

clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b079

Cumulative input power display

1. to 1000.

 

 

1.

 

 

 

 

gain setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b082

Start frequency adjustment

0.10 to 9.99 (Hz)

 

 

0.50

 

 

 

 

b083

Carrier frequency setting

0.5 to 15.0 (kHz) (subject to derating)

 

 

5.0

 

 

 

 

b084

Initialization mode (parameters or

00 (clearing the trip history), 01 (initializing the data),

 

 

00

 

 

 

 

trip history)

02 (clearing the trip history and initializing the data)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b085

Country code for initialization

00 (Japan), 01 (EU), 02 (U.S.A.)

00

 

01

 

02

 

 

b086

Frequency scaling conversion

0.1 to 99.0

 

 

1.0

 

 

 

 

factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b087

STOP key enable

00 (enabling), 01 (disabling), 02 (disabling only the function to stop)

 

 

00

 

 

 

Others

b088

Restart mode after FRS

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting

 

 

00

 

 

 

with active matching frequency)

 

 

 

 

 

 

 

 

 

 

 

 

 

b089

Automatic carrier frequency

00: invalid, 01: valid

 

 

00

 

 

 

 

 

 

 

 

 

 

reduction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b090

Dynamic braking usage ratio

0.0 to 100.0 (%)

 

 

0.0

 

 

 

 

b091

Stop mode selection

00 (deceleration until stop), 01 (free-run stop)

 

 

00

 

 

 

 

b092

Cooling fan control

00 (always operating the fan), 01 (operating the fan only during inverter

 

 

00

 

 

 

 

operation [including 5 minutes after power-on and power-off])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b095

Dynamic braking control

00 (disabling), 01 (enabling [disabling while the motor is topped]), 02

 

 

00

 

 

 

 

(enabling [enabling also while the motor is topped])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b096

Dynamic braking activation level

330 to 380, 660 to 760(V)

 

 

360/

 

 

 

 

 

 

720

 

 

 

 

 

 

 

 

 

 

 

 

 

b098

Thermistor for thermal protection

00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02

 

 

00

 

 

 

 

control

(enabling the thermistor with NTC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b099

Thermal protection level setting

0. to 9999. ()

 

 

3000.

 

 

 

 

b100

Free-setting V/f frequency (1)

0. to "free-setting V/f frequency (2)" (Hz)

 

 

0.

 

 

 

 

b101

Free-setting V/f voltage (1)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

characteristic

b102

Free-setting V/f frequency (2)

0. to "free-setting V/f frequency (3)" (Hz)

 

 

0.

 

 

 

b103

Free-setting V/f voltage (2)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

b104

Free-setting V/f frequency (3)

0. to "free-setting V/f frequency (4)" (Hz)

 

 

0.

 

 

 

b105

Free-setting V/f voltage (3)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

b106

Free-setting V/f frequency (4)

0. to "free-setting V/f frequency (5)" (Hz)

 

 

0.

 

 

 

of V/f

 

 

 

 

 

b107

Free-setting V/f voltage (4)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

setting

b108

Free-setting V/f frequency (5)

0. to "free-setting V/f frequency (6)" (Hz)

 

 

0.

 

 

 

b109

Free-setting V/f voltage (5)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

Free

 

 

 

 

 

 

 

 

 

b110

Free-setting V/f frequency (6)

0. to "free-setting V/f frequency (7)" (Hz)

 

 

0.

 

 

 

 

b111

Free-setting V/f voltage (6)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

 

b112

Free-setting V/f frequency (7)

0. to 400. (Hz)

 

 

0.

 

 

 

 

b113

Free-setting V/f voltage (7)

0.0 to 800.0 (V)

 

 

0.0

 

 

 

 

b120

Brake Control Enable

00 (disabling), 01 (enabling)

 

 

00

 

 

 

 

b121

Brake Wait Time for Release

0.00 to 5.00 (s)

 

 

0.00

 

 

 

 

b122

Brake Wait Time for Acceleration

0.00 to 5.00 (s)

 

 

0.00

 

 

 

 

b123

Brake Wait Time for Stopping

0.00 to 5.00 (s)

 

 

0.00

 

 

 

 

b124

Brake Wait Time for Confirmation

0.00 to 5.00 (s)

 

 

0.00

 

 

 

 

b125

Brake Release Frequency Setting

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

 

0.00

 

 

 

 

b126

Brake Release Current Setting

0.0 to 2.00 x "rated current"

Rated current of inverter

 

Others

b127

Braking frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

 

0.00

 

 

 

b130

Overvoltage suppression enable

00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling

 

 

00

 

 

 

 

 

 

acceleration)

 

 

 

 

 

 

 

b131

Overvoltage suppression level

330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)

 

 

380/

 

 

 

 

 

 

760

 

 

 

 

 

 

 

 

 

 

 

 

 

b132

Acceleration and deceleration

0.10 to 30.00 (s)

 

 

1.00

 

 

 

 

rate at overvoltage suppression

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b133

Overvoltage suppression

0.00 to 2.55

 

 

0.50

 

 

 

 

propotional gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b134

Overvoltage suppression Integral

0.000 to 9.999 / 10.00 to 65.53 (s)

 

 

0.060

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - 9

Page 13
Image 13
Hitachi SJ700-2 Series service manual Free-setting V/f frequency To 400. Hz