Name |
|
| Description |
|
| Display on | Display on | Troubleshooting and corrective action | |
|
|
|
| digital operator | remote operator | ||||
|
|
|
|
|
|
| Check for the noise sources located near the | ||
|
|
|
|
|
|
|
|
| |
Gate array | If an error occurs in the communication |
|
| inverter. | |||||
|
| (Remove noise sources.) | |||||||
communica- | between | the | internal CPU | and | gate |
| GA.COM | ||
| Check whether the communication cable has | ||||||||
tion error | array, the inverter will trip. |
|
|
|
| ||||
|
|
|
| been disconnected. | |||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| (Check the connectors.) |
| When the phase loss input protection |
|
| Check for the phase loss power input. | |||||
Phase loss | has been enabled (b006 = 01), the |
|
|
| (Check the power supply input wiring.) | ||||
inverter will trip to avoid damage if an |
|
| Check the MCB and magnetic contactors for | ||||||
input | phase loss input is detected. The inverter |
| PH.fail | poor contacts. | |||||
protection | trips when the phase loss input |
|
|
| (Replace the MCB and magnetic contactors.) | ||||
| continues for about 1 second or more. |
|
| Check for the noise sources located near the | |||||
|
|
|
|
|
|
|
|
| |
| The inverter | will | trip if the gate | array |
|
| inverter. | ||
|
|
| (Remove noise sources.) | ||||||
Main circuit | cannot confirm the on/off state of IGBT |
|
| ||||||
| Main.Cir | Check the main circuit element for damage. | |||||||
error (*3) | because | of | a | malfunction | due to |
| Check the output circuit for a short circuit. | ||
noise,short or damage to the main circuit |
|
| |||||||
|
|
| (Check the IGBT.) | ||||||
| element. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Check the inverter for abnormality. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| (Repair the inverter.) |
| If instantaneous overcurrent occurs, the |
|
| Check the output circuit for a short circuit. | |||||
| main circuit element temperature is |
|
|
| (Check the output cables.) | ||||
| abnormal, or the main circuit element |
|
| Check for the ground fault. | |||||
IGBT error | drive power drops, the inverter will shut |
| IGBT | (Check the output cables and motor.) | |||||
off its output to protect the main circuit |
| Check the main circuit element for damage. | |||||||
| element. (After tripping because of this |
|
| (Check the IGBT.) | |||||
| protective function, the inverter cannot |
|
| Check the heat sink for clogging. | |||||
| retry the operation.) |
|
|
|
| (Clean the heat sink.) | |||
| The inverter monitors the resistance of |
|
| Check whether the motor temperature is high. | |||||
| the thermistor (in the motor) connected |
|
| (Check the motor temperature.) | |||||
| to the inverter's TH terminal, and will |
|
| Check whether the internal thermistor of the | |||||
Thermistor | shut off the inverter output if the motor |
|
| motor has been damaged. | |||||
temperature rises. |
|
|
|
| TH | (Check the thermistor.) | |||
error |
|
|
|
| |||||
|
|
|
|
|
|
|
| Check whether noise has been mixed in the | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| thermistor signal. |
|
|
|
|
|
|
|
|
| (Separate the thermistor wiring from other |
| When "01" has been specified for the |
|
| wirings.) | |||||
|
|
| Check whether the brake has been turned on | ||||||
| Brake Control Enable (b120), the |
|
|
| and off or not. | ||||
| inverter will trip if it cannot receive the |
|
| (Check the brake.) | |||||
Braking error | braking confirmation signal within the |
|
| Check whether the wait time (b124) is too | |||||
Brake Wait Time for Confirmation (b124) |
| BRAKE | short. | ||||||
| after the output of the brake release |
|
| (Increase the wait time [b124].) | |||||
| signal. |
|
|
|
|
|
|
| Check whether the braking confirmation |
|
|
|
|
|
|
|
|
| signal has been input. |
|
|
|
|
|
|
|
|
| (Check the wiring.) |
| If the EMR signal (on three terminals) is |
|
| Check whether an error has occurred in the | |||||
| turned on when the slide switch (SW1) |
|
| external equipment since the emergency stop | |||||
Emergency | on the logic board is set to ON, the |
|
| EMR | function was enabled. | ||||
inverter hardware will shut off the |
|
| (Recover the external equipment from the | ||||||
|
|
| |||||||
stop (*4) | inverter output and display the error code |
|
| error.) | |||||
| shown on the right. |
|
|
|
| Check for the noise sources located near the | |||
| Malfunction due to incoming noise,in |
|
| inverter.(Remove noise sources.) | |||||
| case EMR terminal is not ON. |
|
|
|
|
| |||
| If overload occurs during the motor |
|
|
|
| ||||
| operation at a very low speed at 0.2 Hz |
|
|
| |||||
or less, the electronic thermal protection |
|
| Check whether the motor load is too high. | ||||||
overload | circuit in the inverter will detect the |
|
| ||||||
protection | overload and shut off the inverter output. |
|
| (Reduce the load factor.) | |||||
(2nd electronic thermal control) |
|
|
|
| |||||
|
|
|
|
| |||||
| (Note that a high frequency may be |
|
|
|
| ||||
| recorded as the error history data.) |
|
|
|
| ||||
| If timeout occurs because of line |
|
|
| Check whether the communication speed | ||||
Modbus | disconnection during the communication |
|
| setting is correct. | |||||
in |
|
| Check whether the wiring distance is | ||||||
communica- |
| NET.ERR | |||||||
display the error code shown on the |
| appropriate. | |||||||
tion error | right. (The inverter will trip according to |
|
| (Check the connections.) | |||||
| the setting of "C076".) |
|
|
|
| Check whether the option board is mounted | |||
|
|
|
|
|
|
|
|
| |
| The inverter detects errors in the option |
| correctly. | ||||||
|
|
| (Check the board mounting.) | ||||||
| board mounted in the optional slot 1. For | to |
| ||||||
Option 1 error |
| Check whether the option board is used | |||||||
| details, refer to the instruction manual for |
|
| correctly. | |||||
| the mounted option board. |
|
|
| |||||
|
|
|
| (Check the instruction manual for the option | |||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| board.) |