Levels and output terminal status

adjustmentMeter Others AdjustmentCommunication function

 

Code

Function name

Monitored data or setting

 

C038

Low-current indication signal

00 (output during acceleration/deceleration and constant-speed operation),

 

 

output mode selection

01 (output only during constant-speed operation)

 

 

 

C039

Low-current indication signal

0.0 to 2.00 x "rated current" (A)

 

detection level

 

 

 

 

C040

Overload signal output mode

00 (output during acceleration/deceleration and constant-speed operation),

 

01 (output only during constant-speed operation)

 

 

 

 

C041

Overload level setting

0.0 to 2.00 x "rated current" (A)

 

 

 

 

 

C042

Frequency arrival setting for accel.

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

C043

Frequency arrival setting for decel.

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

C044

PID deviation level setting

0.0 to 100.0 (%)

 

C045

Frequency arrival setting for

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

acceleration (2)

 

 

 

 

C046

Frequency arrival setting for

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

deceleration (2)

 

 

 

 

C052

Maximum PID feedback data

0.0 to 100.0 (%)

 

C053

Minimum PID feedback data

0.0 to 100.0 (%)

 

C055

Over-torque (forward-driving) level

0. to 200. (%)

 

setting

 

 

 

 

C056

Over-torque (reverse

0. to 200. (%)

 

regenerating) level setting

 

 

 

 

C057

Over-torque (reverse driving) level

0. to 200. (%)

 

setting

 

 

 

 

C058

Over-torque (forward

0. to 200. (%)

 

regenerating) level setting

 

 

 

 

C061

Electronic thermal warning level

0. to 100. (%)

 

setting

 

 

 

 

C062

Alarm code output

00 (disabling), 01 (3 bits), 02 (4 bits)

 

C063

Zero speed detection level

0.00 to 99.99, 100.0 (Hz)

 

C064

Heat sink overheat warning level

0. to 200.0 (°C)

 

C071

Communication speed selection

02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06

 

(19,200 bps)

 

 

 

 

C072

Node allocation

1. to 32.

 

C073

Communication data length

7 (7 bits), 8 (8 bits)

 

selection

 

 

 

 

C074

Communication parity selection

00 (no parity), 01 (even parity), 02 (odd parity)

 

C075

Communication stop bit selection

1 (1 bit), 2 (2 bits)

 

C076

Selection of the operation after

00 (tripping), 01 (tripping after decelerating and stopping the motor), 02

 

(ignoring errors), 03 (stopping the motor after free-running), 04

 

communication error

 

 

(decelerating and stopping the motor)

 

 

 

 

C077

Communication timeout limit

0.00 to 99.99 (s)

 

before tripping

 

 

 

 

C078

Communication wait time

0. to 1000. (ms)

 

C079

Communication mode selection

00(ASCII), 01(Modbus-RTU)

 

C081

[O] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

 

C082

[OI] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

 

C083

[O2] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

 

C085

Thermistor input tuning

0.0 to 999.9, 1000.

 

C091

Debug mode enable

(Do not change this parameter, which is intended for factory adjustment.)

 

C101

Up/Down memory mode selection

00 (not storing the frequency data), 01 (storing the frequency data)

 

C102

Reset mode selection

00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2

 

(enabling resetting only upon tripping [resetting when RS is on])

 

 

 

 

C103

Restart mode after reset

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting

 

with active matching frequency),03(resetting only trip)

 

 

 

 

C105

FM gain adjustment

50. to 200. (%)

 

C106

AM gain adjustment

50. to 200. (%)

 

C107

AMI gain adjustment

50. to 200. (%)

 

C109

AM bias adjustment

0. to 100. (%)

 

C110

AMI bias adjustment

0. to 100. (%)

 

 

 

 

Default

Note

_FF _FEF _FUF

01

Rated current of

inverter

01

Rated current of

inverter

0.00

0.00

3.0

0.00

0.00

100.0

0.0

100.

100.

100.

100.

80.

00

0.00

120.

04

1.

7

00

1

02

0.00

0.

00

Factory setting Factory setting Factory setting Factory setting 00

00

00

00

100.

100.

100.

0.

20.

1 - 12

Page 16