Hitachi SJ700-2 Series service manual Fef Fuf

Models: SJ700-2 Series

1 81
Download 81 pages 46.46 Kb
Page 19
Image 19

 

 

 

 

 

Default

 

 

Code

Function name

Monitored data or setting

 

 

 

 

Note

 

 

 

 

_FF

 

_FEF

_FUF

 

 

 

 

 

 

 

 

 

 

 

H050

PI proportional gain for 1st motor

0.0 to 999.9, 1000.

 

100.0

 

 

 

H250

PI proportional gain for 2nd motor

0.0 to 999.9, 1000.

 

100.0

 

 

 

H051

PI integral gain for 1st motor

0.0 to 999.9, 1000.

 

100.0

 

 

 

H251

PI integral gain for 2nd motor

0.0 to 999.9, 1000.

 

100.0

 

 

 

H052

P proportional gain setting for 1st

0.01 to 10.00

 

1.00

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

H252

P proportional gain setting for 2nd

0.01 to 10.00

 

1.00

 

 

 

motor

 

 

 

constants

 

 

 

 

 

 

 

H060

Zero LV lmit for 1st motor

0.0 to 100.0

 

100.0

 

 

H260

Zero LV lmit for 2nd motor

0.0 to 100.0

 

100.0

 

 

 

Zero LV starting boost current for

 

 

 

 

 

 

Control

H061

0. to 50. (%)

 

50.

 

 

1st motor

 

 

 

 

 

 

 

 

 

 

H261

Zero LV starting boost current for

0. to 50. (%)

 

50.

 

 

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

 

 

 

H070

Terminal selection PI proportional

0.0 to 999.9, 1000.

 

100.0

 

 

 

gain setting

 

 

 

 

 

 

 

 

 

 

 

 

H071

Terminal selection PI integral gain

0.0 to 999.9, 1000.

 

100.0

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

H072

Terminal selection P proportional

0.00 to 10.00

 

1.00

 

 

 

gain setting

 

 

 

 

 

 

 

 

 

 

 

 

H073

Gain switching time

0. to 9999. (ms)

 

100.

 

 

1 - 15

Page 19
Image 19