Code

Function name

 

Monitored data or setting

 

Default

 

Note

d025

User monitor 0

 

-2147483647 to 2147483647 (upper 4 digits including “-“)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d026

User monitor 1

 

-2147483647 to 2147483647 (upper 4 digits including “-“)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d027

User monitor 2

 

-2147483647 to 2147483647 (upper 4 digits including “-“)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d028

Pulse counter

 

0 to 2147483647 (upper 4 digits)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d029

Position setting monitor

 

-1073741823 to 1073741823 (upper 4 digits including “-“)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d030

Position feedback monitor

 

-1073741823 to 1073741823 (upper 4 digits including “-“)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d080

Trip Counter

 

0. to 9999., 1000 to 6553 (10000 to 65530) (times)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d081

Trip monitoring 1

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d082

Trip monitoring 2

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d083

Trip monitoring 3

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d084

Trip monitoring 4

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d085

Trip monitoring 5

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d086

Trip monitoring 6

 

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),

 

 

 

 

 

 

power-on time (hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

d090

Programming error monitoring

 

Warning code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d102

DC voltage monitoring

 

0.0 to 999.9 (V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d103

BRD load factor monitoring

 

0.0 to 100.0 (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d104

Electronic thermal overload monitoring

 

0.0 to 100.0 (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2.2 Function Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Default

 

 

Code

 

Function name

 

Monitored data or setting

 

 

 

 

 

 

 

 

 

 

 

 

_FF

 

_FEF

_FUF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency setting

0.0, "start frequency" to "maximum frequency" (or maximum frequency,

 

 

 

 

 

 

F001

 

 

2nd/3rd motors) (Hz)

 

0.00

 

 

 

 

 

 

0.0 to 100.0 (when PID function is enabled)

 

 

 

 

 

 

F002

Acceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

F202

Acceleration (1) time setting, 2nd

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

F302

Acceleration (1) time setting, 3rd

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

F003

Deceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

F203

Deceleration time setting, 2nd motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

F303

Deceleration time setting, 3rd motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

 

30.00

 

 

 

F004

Keypad Run key routing

00 (forward rotation), 01 (reverse rotation)

 

00

 

 

 

1 - 3

Page 7
Image 7