Hoshizaki KM-201BAH Control Board P01771-02, k Refill Counter S2 dip switch 3 Program Ver

Models: KM-201BWH KM-260BWH KM-201BAH KM-260BAH

1 81
Download 81 pages 49.56 Kb
Page 25
Image 25

S2 Dip Switch Setting

Anti-Slush Control

No. 5

No. 6

 

OFF

OFF

Activated (Ver. 1.0)

ON

OFF

Activated (Ver. 2.0)

OFF

ON

Deactivated

ON

ON

Deactivated

Control Board P01771-02

j) Harvest Promotion Control (S2 dip switch 2) [Program Ver. 3.2]

Do not adjust. This must be left in the factory default position or the unit will not operate properly.

When activated, this control promotes harvest of ice on the evaporator that is hard to remove. If the harvest cycle exceeds 6 minutes, the pump motor starts to operate for a maximum of 3 minutes.

S2 Dip Switch Setting

Harvest Promotion

No. 2

Control

OFF

Activated

ON

Deactivated

k) Refill Counter (S2 dip switch 3) [Program Ver. 3.2]

Do not adjust. This must be left in the factory default position or the unit will not operate properly. The KM-201BAH/BWH and KM-260BAH/BWH do not refill.

l) Harvest Completion Detection Control (S2 dip switch 4) [Program Ver. 3.2]

Do not adjust. This must be left in the factory default position or the unit will not operate properly.

It is deactivated on the KM-201BAH/BWH and KM-260BAH/BWH.

When activated, this control determines whether ice remains on the evaporator at the end of a harvest cycle and at the beginning of a freeze cycle. If ice drops and activates the bin control switch in the last 10 seconds of a harvest cycle, the control determines that ice still remains on the evaporator and extends the harvest cycle for 30 seconds. If the bin control switch is activated at the beginning of a freeze cycle, the control determines that ice still remains on the evaporator and starts a harvest cycle after the minimum freeze cycle time has passed.

S2 Dip Switch Setting

Harvest Completion

No. 4

Detection Control

OFF

Deactivated

ON

Activated

20

Page 25
Image 25
Hoshizaki KM-201BAH, KM-260BAH, KM-260BWH, KM-201BWH Control Board P01771-02, k Refill Counter S2 dip switch 3 Program Ver