(2) "G" Control Board: Auxiliary Code U-1 and Later
At startup, a
Sequence Step |
| LED |
| Energized |
|
|
|
| Time LEDs are On | ||
|
| Components |
|
| Min. |
| Max. | Avg. | |||
|
|
|
|
|
|
| |||||
4 |
| WV |
|
|
|
|
|
| 1 minute | ||
Harvest Cycle |
| 1, 4, 2 |
| Comp, FMR, WV, HGV |
|
| 2 minutes |
| 20 minutes |
| 3 to 5 minutes |
Harvest Pump Timer | 1, 3, 2 |
| Comp, FMR, PM, HGV |
|
| 0 seconds |
| 50 seconds | harvest pump timer | ||
|
|
|
|
|
|
|
|
|
|
| setting |
Freeze Cycle | 1 |
| Comp, FM/FMR, PM, |
|
| 5 minutes |
| freeze timer | 30 to 35 minutes | ||
|
|
|
| LLV |
|
|
|
| setting |
| |
| 1, 4*, 3, 2 Comp, FMR, WV*, PM, |
|
| 10 seconds 20 seconds | *pump‑out timer | ||||||
|
|
|
| HGV |
|
|
|
|
|
| setting |
The
No. of Beeps | Type of Alarm | Notes | |
(every 3 sec.) | |||
|
| ||
1 | High Evaporator Temp. | Check for harvest problem (stuck HGV or relay), hot | |
| (temperature > 127°F) | water entering unit, stuck HM, or shorted thermistor. | |
| (53°C) |
| |
2 | Harvest Backup Timer | Check for open thermistor, HGV not opening, TXV or | |
| (harvest > 20 min. for two cycles | LLV leaking by, low charge, inefficient Comp, or WRV | |
| in a row) | leaking by. | |
3 | Freeze Timer | Check for F/S stuck closed (up), WV leaking by, HGV | |
| (freeze > freeze timer setting for | leaking by, PM not pumping, TXV not feeding properly, | |
| two cycles in a row) | LLV not opening, low charge, HM not bypassing, or | |
|
| inefficient Comp. | |
To reset the above safeties, press the "ALARM RESET" button with the power supply on. | |||
6 | Low Voltage | Red LED turns off if voltage protection operates. | |
| (92Vac±5% or less) | The control voltage safeties automatically reset when | |
7 | High Voltage | voltage is corrected. | |
| (147Vac±5% or more) |
|
Legend:
31