(2) "G" Control Board: Auxiliary Code U-1 and Later

At startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs when the control switch is moved to the "ICE" position. The red LED indicates proper control voltage and remains on unless a control voltage problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup as listed in the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. For details, see "II.B. Sequence of Operation."

Sequence Step

 

LED

 

Energized

 

 

 

 

Time LEDs are On

 

 

Components

 

 

Min.

 

Max.

Avg.

 

 

 

 

 

 

 

1-Minute Fill Cycle

4

 

WV

 

 

 

 

 

 

1 minute

Harvest Cycle

 

1, 4, 2

 

Comp, FMR, WV, HGV

 

 

2 minutes

 

20 minutes

 

3 to 5 minutes

Harvest Pump Timer

1, 3, 2

 

Comp, FMR, PM, HGV

 

 

0 seconds

 

50 seconds

harvest pump timer

 

 

 

 

 

 

 

 

 

 

 

setting

Freeze Cycle

1

 

Comp, FM/FMR, PM,

 

 

5 minutes

 

freeze timer

30 to 35 minutes

 

 

 

 

LLV

 

 

 

 

setting

 

Pump-Out Cycle

 

1, 4*, 3, 2 Comp, FMR, WV*, PM,

 

 

10 seconds 20 seconds

*pumpout timer

 

 

 

 

HGV

 

 

 

 

 

 

setting

The built-in safeties shut down the unit and have alarms as listed below.

No. of Beeps

Type of Alarm

Notes

(every 3 sec.)

 

 

1

High Evaporator Temp.

Check for harvest problem (stuck HGV or relay), hot

 

(temperature > 127°F)

water entering unit, stuck HM, or shorted thermistor.

 

(53°C)

 

2

Harvest Backup Timer

Check for open thermistor, HGV not opening, TXV or

 

(harvest > 20 min. for two cycles

LLV leaking by, low charge, inefficient Comp, or WRV

 

in a row)

leaking by.

3

Freeze Timer

Check for F/S stuck closed (up), WV leaking by, HGV

 

(freeze > freeze timer setting for

leaking by, PM not pumping, TXV not feeding properly,

 

two cycles in a row)

LLV not opening, low charge, HM not bypassing, or

 

 

inefficient Comp.

To reset the above safeties, press the "ALARM RESET" button with the power supply on.

6

Low Voltage

Red LED turns off if voltage protection operates.

 

(92Vac±5% or less)

The control voltage safeties automatically reset when

7

High Voltage

voltage is corrected.

 

(147Vac±5% or more)

 

Legend: Comp–compressor; FM–fan motor; FMR–fan motor-remote; F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve

31

Page 31
Image 31
Hoshizaki KM-901MAH, KM-901MWH, KM-901MRH/3 service manual Control Board Auxiliary Code U-1 and Later