f) LED Lights and Audible Alarm Safeties

(1) "E" Control Board: Auxiliary Code T-0, U-0

At startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs when power is turned off. The red LED indicates proper control voltage and remains on unless a control voltage problem occurs. The green LEDs

1 through 4 energize and sequence from initial startup as listed in the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2.

For details, see "II.B. Sequence of Operation."

Sequence Step

LED

Energized

 

Time LEDs are On

Components

Min.

Max.

Avg.

 

 

1-Minute Fill Cycle

4

WV

 

 

1 minute

Harvest Cycle

1, 4, 2

Comp, FMR, WV,

2 minutes

20 minutes

3 to 5 minutes

 

 

HGV

 

 

 

Freeze Cycle

1

Comp, FM/FMR, PM,

5 minutes

freeze timer 30 to 35 minutes

 

 

LLV

 

setting

 

Pump-Out Cycle

1, 4*, 3, 2

Comp, FMR, WV*,

10 seconds

20 seconds

*pump-out timer setting

 

 

PM, HGV

 

 

 

The built-in safeties shut down the unit and have alarms as listed below.

No. of Beeps

Type of Alarm

Notes

(every 3 sec.)

 

 

1

High Evaporator Temp.

Check for harvest problem (stuck HGV or relay), hot

 

(temperature > 127°F)

water entering unit, stuck HM, or shorted thermistor.

 

(53°C)

 

2

Harvest Backup Timer

Orange "H TIMER" LED on.

 

(harvest > 20 min. for two cycles

Check for open thermistor, HGV not opening, TXV or

 

in a row)

LLV leaking by, low charge, inefficient Comp, or WRV

 

 

leaking by.

3

Freeze Timer

Yellow "F TIMER" LED on.

 

(freeze > freeze timer setting for

Check for F/S stuck closed (up), WV leaking by, HGV

 

two cycles in a row)

leaking by, PM not pumping, TXV not feeding properly,

 

 

LLV not opening, low charge, HM not bypassing, or

 

 

inefficient Comp.

To reset the above safeties, press the "ALARM RESET" button with the power supply on.

6

Low Voltage

Red LED turns off if voltage protection operates.

 

(92Vac±5% or less)

The control voltage safeties automatically reset when

7

High Voltage

voltage is corrected.

 

(147Vac±5% or more)

 

Legend: Comp–compressor; FM–fan motor; FMR–fan motor-remote;

F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve

30

Page 30
Image 30
Hoshizaki KM-901MWH LED Lights and Audible Alarm Safeties, Sequence Step, No. of Beeps Type of Alarm Every 3 sec