Problem

Possible Cause

 

Remedy

 

 

 

 

[2]All ice formed on

l) Refrigerant

1. Low charge.

1. Check for leaks. Recover,

evaporator does not

 

 

repair, evacuate, and

fall into bin in harvest

 

 

recharge.

cycle. (continued)

m)Water Regulating Valve

1. Leaking by in harvest.

1. Check and replace.

 

 

(water-cooled model)

 

 

 

 

 

 

[3]Other.

a) Ice Cube Guide

1. Out of position.

1. Place in position.

 

 

 

 

 

b) Thermostatic Bin

1. Bulb out of position.

1. Place in position.

 

Control

 

 

 

2. Bad contacts.

2. Check for continuity and

 

 

 

 

 

replace. See "IV.C.1.

 

 

 

Thermostatic Bin Control

 

 

 

Check."

 

c) Mechanical Bin Control

1. Movement restricted.

1. Check and free.

 

 

2. Defective.

2. See "IV.C.2. Mechanical

 

 

 

Bin Control Check and

 

 

 

Cleaning."

 

 

 

 

3. Low Ice Production

Problem

Possible Cause

 

Remedy

 

 

 

 

[1] Freeze cycle time is

a) Inlet Water Valve

1. Diaphragm does not

1. Check for water leaks with

long.

 

 

close.

icemaker off.

 

b) Float Switch

1. Float switch does not

1. Clean or replace. See "IV.

 

 

 

move freely or switch

D. Float Switch Check and

 

 

 

defective.

Cleaning."

 

 

 

 

 

c) Evaporator

1. Scaled up.

1. Clean.

 

 

 

 

 

 

 

 

2. Damaged.

2. Replace.

 

 

 

 

 

d) Spray Tubes

1. Dirty.

1. Clean.

 

 

 

 

 

 

 

 

2. Out of position.

2. Place in position.

 

e) Pump Motor

1. RPM too slow.

1. See chart 1.[5].

 

 

 

 

 

 

f)

Condenser (except

1. Air filter or condenser

1. Clean.

 

 

water-cooled model)

clogged.

 

 

 

 

 

 

g) Refrigerant Charge

1. Low charge.

1. Check for leaks. Recover,

 

 

 

 

repair, evacuate, and

 

 

 

 

recharge.

 

 

 

 

 

h) Hot Gas Valve

1. Open.

1. Check and replace.

 

i)

Expansion Valve

1. Bulb loose.

1. Secure bulb.

 

 

 

 

 

 

 

 

2. Operating erratically.

2. Check and replace.

 

 

 

 

 

 

j)

Compressor

1. Erratic or off.

1. See chart 1.[3].

 

 

 

 

 

k) Condenser Water

1. Water regulating valve

1. Adjust or replace. See

 

 

(water-cooled model)

set too high.

"V.J. Adjustment of Water

 

 

 

 

Regulating Valve."

 

 

 

 

 

 

 

 

2. Condenser water

2. Check and get

 

 

 

pressure too low.

recommended pressure.

 

 

 

3. Water temperature out

3. Correct to specification.

 

 

 

of specification.

 

 

 

 

 

 

 

l)

Liquid Line Valve

1. Erratic, sticking.

1. Check and replace.

 

 

 

 

 

m)Headmaster (C.P.R.)

1. Bypassing.

1. Replace.

 

 

(remote condenser

 

 

 

 

unit)

 

 

 

 

 

 

 

65

Page 65