Item

Electrical safety label

Description

 

 

 

1

Main power cabinet high

Provides a reminder to users there are high voltage electrical

 

voltage

components inside the cabinet

 

 

 

2

Do not enter label

Provides a warning to users not to enter while a fire is

 

 

extinguishing

4

Power disconnect label

States that power should be disconnected before maintenance

 

 

is performed

5

Short circuit current label

States that the design of the POD can withstand the available

 

 

fault current and describes the electrical system

6

Arc flash warning

Provides a reminder to users of the danger of arc flash and

 

 

required PPE

 

 

 

Internal panel labels

Front view shown

Item

Electrical safety label

Description

 

 

 

1

Power feeders caution label

Cautions users about phase rotation for all power feeders

2

Wire color code

Lists the 380-415 Y/200-240 V color codes:

 

 

Brown—Phase A/L1

 

 

Black—Phase B/L2

 

 

Grey—Phase 3/L3

 

 

Blue—Neutral

 

 

Green and yellow—Equipment ground

 

 

 

3

Panel schedule/circuit breaker

Lists the layout and designation for all circuit breakers and lists

 

table/fuse list

all fuse types and sizes

Component identification 15