For the location of EPO buttons, see "Life safety component identification (on page 9)."

The EPO system must be reset before you can power up and restart the HP POD 20c. To reset the EPO system:

1.Verify that the key control for the EPO mode is in the Armed position.

2.Press the white EPO Reset button.

If you triggered the EPO system manually, you must reset the EPO button that you pressed to the Active position.

ECS touchscreen and EPO indicators

The ECS touchscreen and EPO indicators are located on the door to the control panel.

The touchscreen enables you to easily configure the environmental parameters, access data, and monitor environmental, life safety, and access control conditions within the HP POD 20c.

The EPO indicators provide EPO status. The EPO key control and EPO reset button enable you to adjust the EPO system mode.

Item

Component

Indicator Color

Description

 

 

 

 

1

Source A available indicator

White

Indicates the EPO power status for main

 

 

 

power feed A

 

 

 

 

2

Source A wrong rotation indicator

Red

Indicates the Source A power phase

 

 

 

rotation is incorrect

 

 

 

 

3

Source B wrong rotation indicator

Red

Indicates the Source B power phase

 

 

 

rotation is incorrect

4

Source B available indicator

White

Indicates the EPO power status for main

 

 

 

power feed B

5

EPO shutdown indicator

Red

Indicates an EPO shutdown or alarm

 

 

 

situation

 

 

 

 

6

EPO armed indicator

White

Indicates that the EPO system is armed and

 

 

 

operational

 

 

 

 

7

EPO reset button

Blue

Resets the EPO system when pressed

Life safety systems 19