Capacities

HP POD 20c capacity limitations

The capacity limitations for the HP POD 20c are separated into two categories: electrical power and mechanical cooling capacities. Both of these categories are interdependent and must be considered in conjunction with the overall customer requirements.

Electrical and mechanical cooling capacities

Feature

Specification

 

 

Critical IT electrical

2 x 320 A feeders at 380-415 VAC WYE, 3-Phase,

connections

4-wire, with equipment grounding conductors 5.1 x

 

10.2 cm (2 x 4 in) conduit fittings per feeder provided

 

 

 

Critical IT power

Non-redundant—263-288 kW

capacity

2N Redundant—132-144 kW

 

 

Mechanical cooling

Not applicable

electrical connections

Power for the cooling system fans comes from the

 

critical IT power feeds.

Mechanical cooling

Non-redundant—300 kW

capacity

N+1 Redundant—250 kW

 

 

 

Power feeders

IMPORTANT: A licensed electrician must connect the power according to all local and national electrical codes, and must comply with manufacturer specifications.

The HP POD 20c has two power feeder couplings that provide the entrance for power to the POD. The power feeders route into the top of each electrical panel on the end of the HP POD 20c.

Power, electrical, and controls 27