Fire alarm panel connections

The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP POD 20c.

Water specifications

The following table describes the chilled water system specifications for the HP POD 20c.

Feature

Specification

 

 

Facility input temperature to the HP POD

12º to 24ºC (55º to 75ºF)

20c

 

Max design pressure

1,034 kPa (150 psi)

HP POD 20c pressure drop

172.4 kPa (25 psi)

HP POD 20c water flow rate

454 lpm (120 gpm*)

Chilled water supply and return

Two DIN PN16 DN80 flanges

connections

 

*Measurement is in US gallons per minute.

Rack specifications

Standard HP POD 20c racks (AT978A)

Feature

Specification

 

 

U height

50U

Width

54.6 cm (21.5 in)

Depth

99 cm (39 in)*

Maximum load weight

1,360.7 kg (3,000 lb)

*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.

Thermal and air flow performance

Maximum thermal and air flow

HP POD 20c specification

performance parameters

 

 

 

Air temperature—Inlet to

Dependent on IT configuration and

rack-mounted components

chilled water inlet temperature

Chilled water temperature

12°C to 24°C (55°F to 75°F)

Total rack-mounted component air

Variable as required to maintain hot

flow

aisle setpoint temperature and

 

dependent on IT configuration

 

 

Heat rejection capacity

300 kW

Environmental specifications

Feature

Specification

 

 

Operating temperature

-28ºC to 54ºC (-18ºF to 130ºF)

Non-operating temperature* -29ºC to 54ºC (-20ºF to 130ºF)

Specifications 75