HP recommends connecting the condensate and humidifier drains from the HP POD 20c to a facility drain to prevent collection of water near the HP POD 20c. For more information on drain connections, see the HP Performance Optimized Datacenter 20c Site Preparation and Requirements Guide.

Hot aisle drains

Heat exchanger condensate drains

Side view shown

Water from natural condensation forms. Condensation from the heat exchangers flows to one of the two condensation drains located at each end of the hot aisle.

IMPORTANT: You might need to connect the HP POD 20c condensate drains directly to the local storm or sanitary drain, depending on the local jurisdictional requirements.

Cold aisle drains

Item

Component

Description

 

 

 

1

Chilled water supply and return

Drains water from the chilled water supply and return header drip

 

header drain

pans in the event a leak develops

 

 

 

2

Humidifier drain

Drains water from the humidifier

Cooling system 64