The Basic System Configuration screen displays the basic alarm parameters, humidifier control, and fan controls. The configured parameters are only used to trigger an ECS alarm. The parameters listed on this screen do not configure the cooling system.

You can select and configure the following parameters:

Cold aisle temperature alarm

Hot aisle temperature alarm

Humidity alarm

Differential pressure alarm

Differential pressure filter alarm

Chilled water supply pressure

Chilled water supply temperature

Chilled water return temperature

Chilled water return pressure

You must select Save to store the parameter changes in the system configuration file. If you do not save your changes, the old parameters stored in the configuration file reload when the system starts.

Configuring the chilled water supply temperature alarm parameters

The current temperature parameters appear on the related buttons.

Environmental control system 48