Feature

Specification

 

 

Facility input temperature to the HP POD

12º to 24ºC (55º to 75ºF)

20c

 

Max design pressure

1,034 kPa (150 psi)

HP POD 20c pressure drop

172.4 kPa (25 psi)

HP POD 20c water flow rate

454 lpm (120 gpm*)

Chilled water supply and return

Two DIN PN16 DN80 flanges

connections

 

*Measurement is in US gallons per minute.

Cooling system components

Each of the three heat exchanger area access hatches are rated NEMA 3R for outdoor use. The exterior of the hatches are coated with a durable finish to protect against corrosion. The access hatches are located on the roof of the POD. The heat exchangers can be accessed from the roof of the POD by removing one of the six access hatches.

Top view shown

Item

Component

Description

 

 

 

1

Heat exchangers

Uses chilled facility water to cool the air in the HP POD 20c

2

Chilled water supply

Provides cooled chilled water from the site chilled water system to the heat

 

header

exchangers

3

Chilled water return

Provides heated chilled water to the return site chilled water system

 

header

 

Cooling system 61