Feature

Specification

 

 

Rack type

HP POD rack

Max number of racks

10

Max U space per rack

50U

Max U space per HP POD 20c

500U

Server capacity

288 kW power capacity

Average capacity per rack

28.8 kW

Peak capacity per rack

69 kW

Voltage to rack

200-240 VAC

Rack configuration

Redundant/Non-redundant

 

capabilities

Total number of PDU's

20 (two per rack)

Max power per PDU

30 A = 17 kW; 60 A = 34 kW

Max load (Chilled POD cooling mode)*

288 kW

Airflow per rack (Chiller POD cooling

1,700 CFM

mode)

 

*Dependent on configuration

 

HP POD 20c lighting

The HP POD 20c includes six LED lights. Three lights are located in the cold aisle and three lights are located in the hot aisle.

The main light switch is located on the ECS control panel door. For more information on the light switch location, see "Life safety component identification (on page 9)."

Two of the six lights are connected to battery backup power, keeping the interior of the HP POD 20c illuminated during a power outage or emergency.

For more information on lighting, see the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.

Power, electrical, and controls 33