Maintenance

Periodic maintenance

Perform periodic inspections to ensure that the HP POD 20c continues to perform according to design parameters. During periodic inspections, pay special attention to electrical connections and wiring.

For more specific maintenance information, see the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.

Sample HP POD 20c maintenance schedule

For detailed maintenance information and schedules, consult with HP services.

The following table is a sample maintenance schedule for an HP POD 20c. For more detailed maintenance information, see the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.

Component to be inspected

Frequency

 

 

Electrical connections and wiring—Visual

Every 30 days

 

 

Electrical connections and wiring—Thermal scans

Every 180 days

Condensation and drainage system (leaks)—Visual

Every 30 days

Condensation and drainage system (leaks)—Functional

Every 90 days

Busway interconnects (tightened)

Every 180 days

EPO system

Every 180 days

Third-party OEM components (fire alarm and suppression system, humidifier,

For more information about the

and so on)

components, see the Operation

 

and Maintenance manual for

 

the HP Performance Optimized

 

Datacenter 20c.

 

 

Maintenance 77